Cable Types; Cable Entries; Dimensions And Weights - ABB ACS800 Series Hardware Manual

Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

122

Cable types

Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-
carrying conductors in raceway or cable or earth (directly buried). For other
conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
Copper cables with concentric copper shield
Max. load

Cable Entries

Input, DC link and motor cable (per phase) terminal sizes, accepted cable diameters
and tightening torques are given below
Frame size
R5
R6
3/0 ... 350 MCM *
* with cable lugs 6...2/0 AWG, tightening torque 14.8...29.5 lbf

Dimensions and weights

Frame size
Drive
R5
R6
Package
R5
R6
Technical data
Cable type
current
A
AWG/kcmil
31
44
57
75
88
101
114
132
154
176
202
224
250 MCM or 2 x 1
251
300 MCM or 2 x 1/0
273
350 MCM or 2 x 2/0
U1, V1, W1, U2, V2, W2, UDC+, UDC-
Wire size
Wire Ø
(UL type 1)
AWG
4...2/0
1.39
2.09
Height
Width
in.
32.03
10.43
38.19
11.81
42.72
15.75
45.08
15.75
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
00096931
.
Tightening
torque
·
in.
lbf
ft
11.1
14.8...29.5
UL type 1
Depth
in.
in.
15.35
17.28
21.61
23.03
Grounding PE
Wire size
Tightening
AWG
4...2/0
4/0
·
ft
Weight
lb
143
220
11
9
torque
·
lbf
ft
11.1
5.9
Noise
dB
70
73

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents