Start-up and use

What this chapter contains

This chapter describes the start-up procedure and use of the drive, and the control
panel control of the line-side and motor-side converters.
Start-up and use
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the
safety instructions can cause injury or death.
Remove the protective film covering the unit.
Perform the start-up procedure as described in the appropriate application program
firmware manual. The parameters of the line-side converter control program
need not be set in a normal start-up procedure or in normal use. However, it is
recommended to set parameter 16.15 START MODE to LEVEL:
• if the motor is started and stopped frequently. This prolongs the lifespan of the
charging contactor.
• when starting the motor without delay after the start command is required.
• If the drive is connected to a common DC bus. Otherwise, the charging resistor
may be damaged.
For setting of parameter 16.15 START MODE, change the control panel to control
the line-side converter as shown on page 100.
Note:
• By default, the control panel controls the RMIO board of the motor-side converter
(ID number 1). If the control panel is set to control the RMIO board of the line-side
converter (ID number 2), the drive does not stop by pressing the control panel
Stop key in local control mode. Have the control panel control the RMIO board of
the motor-side converter in normal use.
• Do not change the ID numbers of the converters from the default settings. If the
ID numbers of the line-side and motor side converters are set equal, the control
panel stops communicating.
Safety instructions
on the first pages of this manual. Ignoring the
99