Command Menu/Dialer-Config/Time Parameter
2.Cellular report date
Command Menu/Dialer-Config/Time Parameter
3.Auto test time
Configuration and CFG-300 LCD Service Tool
0 ->Default
00:30 ->Default
Use this menu to set the
test report date for the cell
phone setup. Set this menu
to 0 if there is no test
reporting for a cell phone,
or if the phone line is a
regular line. Set this menu
from 01 to 28 to schedule a
test for Line 2 on a certain
day of the month. See
section 11.11.5 for more
information.
When a cell phone service
is employed for the panel, it
should only be connected
to telephone line #2 CO
interface. Also, the dial
tone detection feature of
Line 2 should be disabled
for cell phone application.
Use this function to set the
time for the automatic test.
When this test is
performed, the test report is
sent to the monitoring
station. This test must be
performed at least once a
day. The time is in 24 hour
format, which means 00:30
is 30 minutes after
midnight.
The Auto test time can be
configured to:
12:00 a.m. to 5:59 a.m.:
test every 24 hours
6:00 a.m. to 11:59 a.m.:
test every 6 hours
12:00 p.m. to 23:59 p.m.:
test every 12 hours
If the Cellular report date is
set to 0, then the test
alternates between Line 1
and Line 2. See section
11.11.5 for more
information.