Secutron MR-2300 Series Installation And Operation Manual page 84

Led fire alarm control panel
Hide thumbs Also See for MR-2300 Series:
Table of Contents

Advertisement

Command Menu/Dialer-Config/Report Options
4.Aux Disconnect, Cancels Alarm
& Supv Reporting Thru dialer
Command Menu/Dialer-Config/Report Options
5.Dialer operation mode
i
Note:
11.11.4Command Menu/Dialer Config-->Time Parameters
- T i m e P a r a m e t e r -
1 A C - L o s s D e l a y
2 C e l l p h o n e D a t e
3 A u t o - T e s t T i m e
Command Menu/Dialer-Config/Time Parameter
1.AC Loss delay
84
[ ] ENABLE
[X] DISABLE ->Default
[X] (U)DACT ->Default
[ ] DACT
Refer to Using the Keypad to Program the MR-2300 on page 63 for detailed
instructions on making menu selections.
0 ->Default
Configuration and CFG-300 LCD Service Tool
If this function is enabled,
pressing AUXILIARY
DISCONNECT (see 9.3.6
Auxiliary Disconnect Button
on page 49) blocks the
alarm and supervisory
events from being reported
through the built-in dialer.
Use this menu to select the
functionality of the dialer. In
DACT mode only common
trouble/alarm/supervisory
are reported while in
UDACT mode all point
information is reported
Use this menu to delay the
reporting of AC loss trouble
on the dialer for the
programmed time period.