The following table describes the cables to be prepared by yourself in the 4G LTE network scenario.
No. Cable
Three-phase AC power
1
cable
Peripheral RS485
2
communications cable
3
Cabinet PE cable
Network cable from the
4
PoE module to the CPE
Single-phase AC power
5
cable
(Optional) 24 V DC
6
output power cable
Recommended Model or Specifications
•
Three-core (L1, L2, and L3) outdoor
armored copper cable
•
When the rated AC voltage on the LV
side of the transformer station is less
than or equal to 600 V, the operating
voltage between the three-phase AC
power cable and the ground should be
greater than or equal to 600 V.
•
When the rated AC voltage on the LV
side of the transformer station is greater
than 600 V and less than or equal to
800 V, the operating voltage between
the three-phase AC power cable and the
ground should be greater than or equal
to 1000 V.
Computer cable (DJYP2VP2-22 2x2x1) or
armored shielded twisted pair that can be
used outdoors, as well as OT-M4 terminals
Outdoor copper cable and OT-M6 terminals
A 20 m (65.62 ft) long network cable
delivered with Huawei CPE (If the length is
insufficient, prepare a cable with the same
specifications as a peripheral network
cable.)
•
Standard connection: two-core outdoor
armored copper cable
•
Connection through a tube: single-core
outdoor copper cable
•
Operating voltage to the ground ≥ 300 V
•
Standard connection: two-core outdoor
armored copper cable
•
Connection through a tube: single-core
outdoor copper cable
•
Operating voltage to the ground ≥ 300
V
10
Cross-sectional Area
Range of the Cable
(Recommended Value)
•
2
8–10 mm
(10 mm
•
8 AWG
•
2
2
0.5–1 mm
(1 mm
•
20–18 AWG (18 AWG)
•
2
6–16 mm
(16 mm
•
10–6 AWG (6 AWG)
N/A
•
2
2
4–6 mm
(4 mm
)
•
12–10 AWG (12 AWG)
•
2
2.5–4 mm
(2.5 mm
•
14–12 AWG (14 AWG)
2
)
)
2
)
2
)