LG PAHCNM000 Owners & Installation Manual page 44

Ahu control kit
Table of Contents

Advertisement

HMI SETTINGS
44
• Holding Register
Address
No.
Hexadecimal
Decimal
1
0x0001
1
2
0x0002
2
3
0x0005
5
4
0x0006
6
5
0x0007
7
6
0x0008
8
35
0x0022
34
36
0x0023
35
37
0x0024
36
38
0x0025
37
39
0x0026
38
40
0x0027
39
42
0x0029
41
43
0x002A
42
44
0x002B
43
45
0x002C
44
46
0x002D
45
47
0x002E
46
48
0x002F
47
49
0x0030
48
50
0x0031
49
CAUTION
!
Abnormal operation may occur if set outside the defined range.
Register
High
40002
Operation mode setting
40003
Airflow setting
40006
Target cooling temperature setting
40007
Target heating temperature setting
40008
Target cooling humidity setting
40009
Target heating humidity setting
40035
Return air fan (high) frequency setting
40036
Return air fan (medium) frequency setting
40037
Return air fan (low) frequency setting
40038
Supply air fan (high) frequency setting
40039
Supply air fan (medium) frequency setting
40040
Supply air fan (low) frequency setting
40042
Cooling outside air damper opening setting
40043
Cooling exhaust damper opening setting
40044
Cooling mixed damper opening setting
40045
Heating outside air damper opening setting
40046
Heating exhaust damper opening setting
40047
Heating mixed damper opening setting
40048
Fan outside air damper opening setting
40049
Fan exhaust damper opening setting
40050
Fan mixed damper opening setting
Data Bit
Low
heating / 3: dehumidification / 4:
outdoor air / 5: fan / 6: reheating
Notes
0: not used / 1: cooling / 2:
0: high / 1: medium / 2: low
18~30 (18) [°C] x 10
18~30 (30) [°C] x 10
30~80 (50) [%] x 10
30~80 (50) [%] x 10
30~60 (50) [Hz]
30~60 (40) [Hz]
30~60 (30) [Hz]
30~60 (50) [Hz]
30~60 (40) [Hz]
30~60 (30) [Hz]
Opening range (0-90) [˚]
Opening range (0-90) [˚]
Opening range (0-90) [˚]
Opening range (0-90) [˚]
Opening range (0-90) [˚]
Opening range (0-90) [˚]
Opening range (0-90) [˚]
Opening range (0-90) [˚]
Opening range (0-90) [˚]

Hide quick links: