CAUTION
!
• Smoke Control mode must be used in conjunction with fire extinguishing equipment in the
building or facility.
• Damper or fan operation should be set based on the building structure and the fire plan.
- If these are set incorrectly, the inability to control smoke could result in physical injury or
property damage.
• When disabling Smoke Control mode, be sure to check whether there is an actual fire
before disabling it.
- Disabling Smoke Control mode during a fire could result in physical injury or property
damage.
5-1-5. Test Run Setting
• Run the 'Test Run Setting' icon on the Installer Setting screen to enable test settings.
After the test run has completed, you must disable the test run setting to return to
normal operation.
11Hz
21Hz
20°
20°
20°
Item
Sets the operating Hz of the supply air fan when in Smoke
Supply air fan
Control mode.
- Setting range: 0-60 Hz
Item
Test Run Setting Sets whether test run is enabled.
Sets the operating status for the return air fan in Test Run
Return Air Fan
mode.
- Setting range: 0-60 Hz
Sets the operating status for the supply air fan in Test Run
Supply air fan
mode.
- Setting range: 0-60 Hz
Sets the operating status for the outdoor air damper in
Outdoor air (OA)
Test Run mode.
damper
- Setting range: 0-90°
Sets the operating status for the exhaust air damper in
Exhaust air (EA)
Test Run mode.
damper
- Setting range: 0-90°
Item
Sets the operating status of the mixed damper in Test Run
Mixed (Mix)
mode.
damper
- Setting range: 0-90°
Sets the operating status of the humidification valve in
Humidification
Test Run mode.
valve (voltage)
- Setting range: 0-10 V
Sets the operating status of the humidification valve in
Humidification
Test Run mode.
valve (contact)
- Setting: Open, Short
Sets the operating status of the heater valve in Test Run
Heater valve
mode.
(voltage)
- Setting range: 0-10 V
Sets the operating status of the heater valve in Test Run
Heater valve
mode.
(contact)
- Setting: Open, Short
HMI SETTINGS
Description
Description
Description
37