AHU CONTROL KIT SETTINGS
14
EEV Module
Capacity Settings
Use DIP switch SW1 to set the capacity.
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
* When connecting a high-capacity EEV kit (PRLK396A0, PRLK594A0), set the capacity to
56.4 kW.
Address Setting
DIP switch SW2 is the address setting function. When the product is shipped from the factory,
the addresses are set as follows.
EEV #1,2,3 are included and EEV #4,5,6 are optional.(After purchasing separately, additional
setting required.)
Sequence
1
EEV #1
OFF
EEV #2
OFF
EEV #3
OFF
EEV #4
OFF
EEV #5
ON
EEV #6
ON
(EEV Module)
2
3
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
SW2
2
3
4
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
SW1
4
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Address
Internal address 0
Internal address 1
Internal address 2
Internal address 3
Internal address 4
Internal address 5
Capacity [kW (kBtu/h)]
2.1 (7)
2.5 (9)
3.5 (12)
5.6 (18)
7.1 (24)
8.2 (28)
10.6 (36)
12.3 (42)
14.1 (48)
22.4 (76)
28.0 (96)
33.6 (115)
39.2 (134)
44.8 (153)
50.5 (172)
56.4 (192)
Remark
EEV #1,2,3
Included
EEV #4,5,6 Optional :
Additional setting required