3-5. Damper
• Run the 'Damper' icon to set the damper's opening value.
• Use the 'Mode' and 'Input' icons to set the damper opening value by operation mode.
- Mode: You can enter damper values for Cooling, Heating, and Vent modes.
- Automatic: Entering the value for either the outdoor air, exhaust, or mixed damper
automatically sets the remaining damper values.
- Manual: You must manually enter the opening values for the outdoor air, exhaust and
mixed dampers.
3-6. Humidity
• Run the 'Humidity' icon to set the target humidity value.
• Humidity setting range: 30-80%
(Set humidity display window)
3-7. Control Mode
• Run the 'Control Mode' icon to set local, remote, and scheduled operation.
• When Local Mode is set, the control function is performed through the HMI installed in the
Control Kit, and only remote monitoring is possible.
• When Remote Mode (contact, modbus, LGAP) is set, the air conditioner can only be
controlled remotely and only status monitoring is possible in the HMI, and the remaining
functions are disabled.
• Scheduled operation is only available when Control Mode is set to Schedule.
(Set humidity manual input window)
HMI SETTINGS
31