Connection scheme and fan motor absorption
( * ) Inner protection thermal contacts
The thermal contacts are temperature sensing, switching ele-
ments built directly into the windings of the motors. They interrupt
an electrical contact when maximum admissable sustained tem-
perature has been reached.
The thermal contacts must be connected to the control circuit of
the mains contactor to prevent automatic reconnection of the
motor in the event of a fault.
Model ICE
06 08 10 12
Fan motors
n. x ø mm
1x450
Absorption
A
(q)
W
A
0,66
(Y)
W
Electric heater connection schemes and electric power
Model with ø 450 mm fan motor
Caution
Application of adequate thermal control systems on feeder lines is mandatory.
Performance of all electric heaters must be periodically controlled to avoid damage due to ice build-up.
The manufacturer is not liable in any way for defects caused by non detected malfunctions.
High speed
q connection
400V/3/50Hz
41x
42x
43x
44x
06 08 10 12
06 08 10 12
06 08 10 12
2x450
3x450
4x450
1,1
2,2
3,3
4,4
540
1080
1620
2160
1,32
1,98
2,64
360
720
1080
1440
Caution
To avoid possible motor damage strictly follow the electric sche-
mes shown.
Before using motor speed control systems verify the compatibility
with the motors; non compatible systems may damage motors or
increase noise level; the manufacturer will not be responsible for
model performance with speed control systems.
51x
52x
53x
54x
06 08 10 12
06 08 10 12
06 08 10 12
06 08 10 12
1x560
2x560
3x560
4x560
2,2
4,4
6,6
1150
2300
3450
4600
1,3
2,6
3,9
740
1480
2220
2960
400V/3/50 Hz Connection (preset)
RBA - High power electric heaters in coil
RBB - Low power electric heaters in coil
RSA - High power electric heaters on drip tray
RSB - Low power electric heaters on drip tray
ICE model ø 450
06 08 10 12
Total power (W)
5040
Low speed
Low speed
q connection
Y connection
230V/3/50Hz
400V/3/50Hz
62x
63x
64x
06 08 10 12
06 08 10 12
06 08 10 12
2x630
3x630
4x630
8,8
7,4
11,1
14,8
3500
5250
7000
5,2
4,4
6,6
8,8
2700
4050
5400
41B
42A
43A
42B
43B
06 08 10 12
06 08 10 12
06 08 10 12
10200
15000
www.modine.com
65x
06 08 10 12
5x630
18,5
8750
11
6750
44B
44B
19800
7