Do you have a question about the POWERLINE RT PLUS 6000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ever POWERLINE RT PLUS 6000

  • Page 2: Table Of Contents

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual TABLE OF CONTENTS INTRODUCTION ..................................3 GENERAL FEATURES OF THE UPS UNIT ........................4 SAFETY INSTRUCTIONS AND RECOMMENDATIONS ....................5 TECHNICAL DESCRIPTION ............................. 11 UNPACKING THE PRODUCT ............................11 What’s in the box? ................................. 11 ELEMENTS OF THE UPS –...
  • Page 3: Introduction

    This manual contains all relevant information to ensure correct and safe operation of the unit. Please read this manual carefully and thoroughly prior to using the EVER POWERLINE RT PLUS unit. This will help you operate the unit correctly and safely.
  • Page 4: General Features Of The Ups Unit

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual GENERAL FEATURES OF THE UPS UNIT The POWERLINE RT PLUS UPS units are ON-LINE (VFI) class devices, designed to work with equipment supplied from ~ 230 VAC single-phase electric power mains.
  • Page 5: Safety Instructions And Recommendations

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual SAFETY INSTRUCTIONS AND RECOMMENDATIONS A) General considerations CAUTION! Before starting the procedures described in this manual, please read the general safety instructions (including the instructions found in this document), health & safety information, environmental protection information and legal regulations that may apply.
  • Page 6 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual CAUTION! Opening the unit’s casing may result in electric shock. CAUTION! Do not touch any electrical connectors, terminals and internal metal elements, unless power supply has been properly disconnected. CAUTION! All openings and spaces designed to provide access to the unit's electrical connections must remain covered (with applicable covers).
  • Page 7 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual CAUTION! The UPS may only be connected to a power system with indicated rated voltage, with a suitable grounding connection installed. The facility's electrical system to which the UPS unit is connected must be fitted with overload and short-circuit protection.
  • Page 8 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual  The electric system's grounding conductor leads the leakage current away from the receivers. The leakage currents of all loads connected to the UPS unit's output are combined in the UPS unit's power lead. The summary leakage current may trigger protective devices (RCD) and result in disconnecting power to the loads.
  • Page 9 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual  WARNING: This is a C3 category UPS. For commercial and industrial use in secondary environment. Additional precautions or limitations in installation may be required to prevent the emission of interferences.
  • Page 10 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual E) Transport and packaging requirements  Exercise particular care when transporting the equipment, due to its heavy weight.  Heavy equipment must be moved by at least two or more persons.
  • Page 11: Technical Description

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual TECHNICAL DESCRIPTION UNPACKING THE PRODUCT The UPS unit must be properly examined upon delivery or handover. Although the product is carefully packaged, the appliance could have been damaged due to shocks experienced during transport.
  • Page 12: Elements Of The Ups - Rear Panel

    Figure 1 present the elements found in rear panels of POWERLINE RT PLUS 6000 / 10000 units. Fig 1: View of the rear panel of POWERLINE RT PLUS 6000 /10 000 1. Intelligent card slot (SNMP card, 7. Parallel card (optional) dry contact) 8.
  • Page 13: Battery Module Design - Rear Panel

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual BATTERY MODULE DESIGN – REAR PANEL Figure 2 present the elements found in rear panels of battery module for POWERLINE RT PLUS 6000 / 10000 units. Fig 2: View of the rear panel of the battery module for POWERLINE RT PLUS 6000 /10 000 1.
  • Page 14: How It Works

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 4: View of the PDU - rear panel 1. Non-controlled output sockets: 3. Maintenance bypass switch 4. Maintenance switch cover 2x IEC 320 C13 (10 A) 1x IEC 320 C19 (16 A) 5.
  • Page 15 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 5: View LCD POWERLINE RT PLUS 6000 /10 000 Table 1. Functions of the control panel buttons Button Function Descriptions When the unit is powered on and stayed in Bypass mode, press this Turn on button for >1s can turn on the...
  • Page 16: User Interface Menu Structure

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual mode, buzzer will work again Press this button for > 100ms & < 2s to exit the present menu to Exit main default system status display menu or the higher level menu without...
  • Page 17: Ups Status Menu

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual By press <1s to the next windows in the submenu. When pressing <1s the display would enter to selected next menu. To go back to the previous main menu window, press for at least 1 s.
  • Page 18: Event Log Menu

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 7: Status menu Event log menu (<1s) on the menu of “Event log”, the display would enter the next By pressing event menu tree. All the previous events, alarm and fault have been recorded here. The information includes the illustration, the event code, and the precise time of UPS when the event happened (fig.
  • Page 19: Measurements Menu

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 8: Event log menu Measurements menu (< 1s) on the menu of “Measurement”, the display would enter the By pressing next measurement menu tree (fig. 9). This menu displays the following values:...
  • Page 20: Control Menu

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 9: Measurements menu Control menu To enter the next Control menu window, press in the Control menu (fig. 10). This menu allows the user to activate the following operations: 1.
  • Page 21 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual the alarm and will go back to the bypass mode. Before manually running the UPS unit, check and remove the cause of the failure. 4. Event log reset: removing all saved failures and errors, which occurred during the operation of the UPS unit, from its memory.
  • Page 22: Identification Menu

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Identification menu To enter the next Identification menu window, press (< 1s) in the Identification menu (fig. 11). This menu shows information on the type and model of the UPS unit, its serial number and the version of the currently installed software.
  • Page 23 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 12: Setting menu tree www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2020-03-20 13:06...
  • Page 24 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 13: Set rated output voltage value Pomoc Techniczna, tel.: +48 61 6500 400 www.ever.eu 2020-03-20 13:06...
  • Page 25: Operation Modes And Warnings

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual OPERATION MODES AND WARNINGS Depending on the current operation mode or the indicated warning, a relevant graphical symbol appears in the lower left part of the screen. Table 4 presents the UPS POWERLINE RT PLUS functional states set, including symbols shown and their descriptions.
  • Page 26 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual ECO mode (unavailable in the parallel operation of UPS units). A power saving, high efficiency mode. If, after switching the UPS unit on in the ECO mode, the parameters of power from the mains (voltage and frequency) meet the standard values, receivers are powered from the mains via an internal filter.
  • Page 27: Protection

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual battery symbol is shown and the UPS unit generates a sound. In case of occurring malfunctions or power loss, receivers will not be powered. UPS Parallel. Using two or three UPS for heavy load or redundancy. See chapter : ”PARALLEL SYSTEMS”.
  • Page 28: Against Overvoltage (Anti-Surge)

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Against overvoltage (Anti-surge) The UPS unit is equipped with anti-surge protection on input to protect circuits of the connected load(s) against potential voltage surges resulting from weather conditions and interference in the power network.
  • Page 29: Ups Unit Instalation

    UNPACKING THE PRODUCT The UPS unit must be properly examined upon delivery or handover. Although ever care has been taken to ensure proper and safe packaging, the product may have suffered damage due to incorrect conditions in transit. Should any product damage be discovered, the carrier or the vendor must be notified immediately.
  • Page 30: Instaling The Ups Unit

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual INSTALING THE UPS UNIT When selecting the place and method of installation, always take into consideration the considerable weight of the UPS unit. The UPS unit should only be used in premises where the dust, temperature, and humidity levels are within the specification.
  • Page 31: Backfeed Protection

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual CAUTION! Connecting of the UPS unit may be carried out only by suitably qualified service technicians, with professional licences required law. CAUTION! The UPS is disconnected from the mains only when the power lead is disconnected removed from the mains socket.
  • Page 32: Installation Of The Ups With A Battery Module

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual B – Remote coil switch Q – Main magnetic/thermal switch T- Power supply contact: For 6k 208-240 V; 63 A For 10k 208-240 V; 100 A Fig 15: Backfeed protection INSTALLATION OF THE UPS WITH A BATTERY MODULE The UPS unit doesn't have internal batteries.
  • Page 33 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual 3. Connect the battery module's terminal to the UPS battery terminal (fig. 18). Fig 18: Connecting the battery module terminal to the UPS 4. Remove the cover of terminal block (fig. 19).
  • Page 34: Installation Of The Ups With A Battery Module - Rack Version

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual INSTALLATION OF THE UPS WITH A BATTERY MODULE – RACK VERSION CAUTION! Taking into account the considerable weight of the devices, we recommend that two persons work together to install the UPS and the battery module in the rack cabinet.
  • Page 35: Disconnecting The Battery Module

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual 4. Slide the battery module into the bottom installation rails and fix with bolts (Fig. 23). Installation of the battery module inside the cabinet 5. Slide the UPS into the upper installation rails and fix with bolts.
  • Page 36: Installation Of The Pdu (Optional Equipment) - Tower Version

    6. Connect the L, N and protective ground wires to the connection terminals of the UPS IN and UPS OUT connectors located on the rear PDU panel. Depending on the power supply model (POWERLINE RT PLUS 6000 / POWERLINE RT PLUS 10000), use the appropriate set of cables (Fig. 26).
  • Page 37 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual 7. Install mounting bracket to PDU (fig. 27) Fig 27: Mounting the bracket 8. Install PDU to UPS by M4 screws on the left side of the UPS (fig. 28).
  • Page 38 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual 10. Remove the cover of terminal blocks in front PDU (fig. 30) Fig 30: Remove the cover PDU – front panel 11. To the connection terminals located on the front panel of the PDU connect the output and input (power) cables fig.
  • Page 39: Installation Of The Pdu (Optional Equipment) - Rack Version

    6. Connect the L, N and protective ground wires to the connection terminals of the UPS IN and UPS OUT connectors located on the rear PDU panel. Depending on the power supply model (POWERLINE RT PLUS 6000 / POWERLINE RT PLUS 10000), use the appropriate set of cables (fig. 26) 7.
  • Page 40: Starting Up The Ups Unit (Power Supply From The Mains)

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 34: Installation PDU 9. Connect the PDU cables to the connection terminals located on the back panel of the UPS (Fig. 14). Connect the L and N wires of the UPS IN socket...
  • Page 41: Starting The Ups Up From The Battery (Cold Start)

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual 4. Make sure no active alarms or messages are displayed on the screen. If any such alarms or messages are present, check their meaning in the "Diagnostics of errors reported by the UPS”.
  • Page 42: Switching From Bypass Mode (Service Bypass) To Mains Mode - By Means Of Pdu

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual If switched to BYPASS, the receivers connected to the IEC 320 C13 output sockets in UPS will cease to be powered. The following steps must be done to switch a UPS operating in MAINS (normal) mode to service BYPASS mode: 1.
  • Page 43: Installation Parallel Card

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual the mains power quality parameters. A combination of several UPS power systems may be considered in order to achieve:  increased load capacity for a BATTERY power supply system (to multiply the total...
  • Page 44 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 35: Remove cover 4. Remove the cover of “parallel box”, then release the “flat cable” from “parallel box” (fig. 36). Note: please, make sure that the “flat cable” could not drop into the case.
  • Page 45: Installation Of The System

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual 7. Install ‘cable locker’ to protect the ‘parallel cable’ for each UPS (fig. 39) Fig 39: Install cover INSTALLATION OF THE SYSTEM CAUTION! Any installation work should be carried out only by suitably qualified service technicians, with professional licences required by law.
  • Page 46 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 40: Parallel installation diagram. Pomoc Techniczna, tel.: +48 61 6500 400 www.ever.eu 2020-03-20 13:06...
  • Page 47: System Start-Up

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Fig 41: Installation diagram of the POWERLINE RT PLUS UPS units in the parallel system SYSTEM START-UP CAUTION! Before operating the UPS unit always make sure whether the units have been correctly installed, in line with the installation recommendations.
  • Page 48: Switching Off The System

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual 4. Press the button continuously for more than 1 second for one UPS of the system, then the system will turn to line mode. 5. Check if the difference between output voltages of the two UPS units is lower than 0,5 V (L of the first unit with L of the second unit).
  • Page 49: Additional Functionalities Of The Ups Unit

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual ADDITIONAL FUNCTIONALITIES OF THE UPS UNIT DRY CONTACTS The UPS is equipped with two dry contacts ( DRY IN, DRY OUT), by which it is possible to signaling (explicitly assigned) states of the UPS. Dry contacts can by configuration: configuration NO (a normally open) or NC (a normally closed) can be made via the RS232 communication interface and software PowerSoft.
  • Page 50: Communication With External Management/Control Systems

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual COMMUNICATION WITH EXTERNAL MANAGEMENT/CONTROL SYSTEMS To establish communication between the PC and the UPS, the user can choose to use the RS232 or USB interface or the Ethernet port (optional equipment).
  • Page 51: Installation Of The Management Card

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Installation of the management card 1. Switch the unit off. 2. Switch the UPS unit's input protections. 3. Wait around 30 seconds (time needed for unloading the unit’s internal capacity).
  • Page 52: Operating Instructions

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual OPERATING INSTRUCTIONS CAUTION! The UPS is a class C3 device. In domestic environment, the UPS may interfere with reception of radio waves so the user may be forced to implement additional preventive measures CAUTION! There are no user-serviceable parts inside the UPS unit.
  • Page 53: Testing Batteries

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual TESTING BATTERIES Before testing batteries check if:  The UPS unit operates in the normal mode, without any active alarm,  the load connected to the UPS unit is higher than 10%.
  • Page 54: Storage, Maintenance And Transport

    5 years. The device should be transported in its original packaging, under conditions specified in the product specification. EVER Sp. z o.o. shall not be liable for mechanical damages arising during the transport of the appliance without its original packaging.
  • Page 55 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual presence of hazardous materials and components, and the improper storage and processing of such equipment. Act dated July 29, 2005 on used electric and electronic equipment Art. 22.1 Item 1,2.
  • Page 56: Technical Parameters

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual TECHNICAL PARAMETERS POWERLINE RT PLUS PARAMETERS \ TYPE POWERLINE RT PLUS 6000 POWERLINE RT PLUS 10 000 Part number T/PWPLRT-116K00/00 T/PWPLRT-1110K0/00 Output Power (Apparent / Active) 6 kVA / 6 kW...
  • Page 57 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual POWERLINE RT PLUS PARAMETERS \ TYPE POWERLINE RT PLUS 6000 POWERLINE RT PLUS 10 000 Part number T/PWPLRT-116K00/00 T/PWPLRT-1110K0/00 Output Power (Apparent / Active) 6 kVA / 6 kW 10 kVA / 10 kW...
  • Page 58: Diagnostics Of Errors Reported By The Ups

    EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual The permitted maximum load of the power supply unit decreases with the height above the sea level above the limit specified above. The range of input voltage depends on tle load: Load 0 –...
  • Page 59 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual ON Maintenance Bypass UPS was manually commanded to switch to Bypass (Orange) LED bypass and will remain in bypass until Check the maintain bypass switch status is on commanded out of bypass...
  • Page 60 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual BUS Short Fault (Red) LED is Indicates that the BUS voltage decrease very Contact your service representative fast Beep continuous. Code: F024 BUS Softstart Fail Fault (Red) LED is Indicates that the BUS could not soft start...
  • Page 61 EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual Parallel system battery status Fault (Red) LED is flash UPS1 connect battery,UPS2 without battery Check battery connect status 1 beep every 1 second Code: A0E6 Line input different Fault (Red) LED is flash Parallel system,UPS1 line ok,UPS2 line loss...
  • Page 62: Legal Regulations And Warranty

    EVER Sp. z o.o. shall not be liable for any direct, indirect, extraordinary, coincidental, or consequential losses resulting from the use of the UPS unit, even if the user has not been notified of the possibility of such losses being incurred.

This manual is also suitable for:

Powerline rt plus 10000