SWITCHING FROM THE UPS POWER TO THE MAINS POWER LINE ............ 5 SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER ............ 6 TECHNICAL FEATURES ..........................7 TECHNICAL SPECIFICATIONS ........................7 NOTES ................................... 7 Technical support, tel.: +48 61 6500 400 www.ever.eu 2016-01-18 05:42...
CAUTION! Read and understand the Instruction Manual for this UPS before attempting the switching operation. OPERATING THE EXTERNAL BYPASS SYSTEM Figure 1. Installation diagram of the POWERLINE 33 60-140 kVA UPS. www.ever.eu Technical support, tel.: +48 61 6500 400 2016-01-18 05:42...
Page 4
Keep the Fsb links outside of the UPS switching room when powering the receivers from the UPS. Fsb, Qsb – Operated by trained personnel only; Incorrect use may damage the UPS Technical support, tel.: +48 61 6500 400 www.ever.eu 2016-01-18 05:42...
5. Turn off the switch disconnector Qout on the UPS output line. 6. Turn off the switch fuse Fm on the UPS input line (also turn off Fb if the UPS has a separate BYPASS line option). www.ever.eu Technical support, tel.: +48 61 6500 400...
CAUTION! Once the procedure for restoring the UPS power has been completed, secure the disconnectors and fuses on the external bypass line from inadvertent switching on by unauthorised personnel. Technical support, tel.: +48 61 6500 400 www.ever.eu 2016-01-18 05:42...
POWERLINE 33 (60-100kVA) POWERLINE 33 (120-140kVA) Dimensions 1050 x 660 x 270 mm 1250 x 660 x 270 mm (height × width × depth) Net weight 48 kg 60 kg NOTES www.ever.eu Technical support, tel.: +48 61 6500 400 2016-01-18 05:42...