ELECTRIC CONTROL PANEL FOR THE EN12845 ELECTRIC FIRE-FIGHTING PUMP

8.1
Overview
The control panel for the electric fire-fighting pump installed as a standalone device or with other pressure modules, was
designed in compliance with the requirements of the fire-fighting standard UNI EN 12845.
After suitable modification, the panel is also available in a version for fire-hydrant networks, characterized by the automatic
shutting off of the pump after the pressure has remained constantly above the starting pressure of the pump itself for the length
of time specified by local regulations (the default setting is 20 minutes). For editing follow the instructions described in chapter
8.8.1. Motor overload protection is ensured by high breaking capacity fuses.
8.2
Restrictions of use, technical data
Product in standard version.
Ambient storage temperature:
Ambient operating temperature:
Voltage rating:
Max power:
Current rating:
Auxiliary circuit voltage:
Relative humidity:
Protection class:
Elevation:
Starts per hour:
Coating on structure:
Refer to the wiring diagram supplied together with the product for further details.
Dusty environments with the presence of sand, or damp environments such as at the seaside, may
ATTENTION
cause premature deterioration, compromising regular operation.
Install the control panel in an indoor area protected against the weather.
1
Fig.2
-10°C to +50 °C
+4°C to +40 °C
1 x 230Vac +/- 10%, 50Hz (Single-phase)
3 x 400Vac +/-10%, 50Hz (Three-phase)
See rating plate on control panel
See rating plate on control panel
12/24 Vac, see diagram of control panel
5% to 40% provided that no condensation occurs.
IP54 (optional IP55)
max 1000 m ASL
Do not exceed the number of starts per hour recommended in the electric pump
specifications.
RAL7035, not suitable for exposure to weathering
1 - Signal and control keypanel
Display, main signals, manual start button, manual stop button and lamp efficiency
A
test button.
2
2 - Measuring instrument
Amperometer
3 - Key-operated 3-position selector switch "Manual - Automatic- 0"
3
- "MAN" (MANUAL): The motor can be started and stopped manually.
- "AUT" (AUTOMATIC): The motor is started via a pressure switch. Manual shut-off,
with the exception of the electric pump version for fire-hydrant networks.
- "0" (DISABLED): Electric pump disabled. If the motor is running, it stops
ON
immediately.
4 - Main door-lock switch.
Main door-lock switch which acts as a cut-off and emergency stop device. It can be
4
padlocked in its "OFF" position.
GEN_0014_B_SC
68