XNX Universal Transmitter
20 mA/HART Output
All XNX Transmitters provide a 20mA Current Loop with HART
Communication which can be user configured for Sink, Source
(3-Wire) or Isolated (4-Wire) electrical interface based on
installation requirements.
The 20mA current loop output provides an analog indication of
special states, a proportional output to gas concentration and
overrange indication as shown in the table below. In the event of
a simultaneous alarm and fault, an alarm condition will always
override fault or warning state.
Output
1.0 mA
2.0 mA
3.0 mA
4-20 mA
Gas Concentration
21 mA
*Alarm conditions always take priority over faults and warnings.
HART Protocol provides communications with the transmitter
from a remote control system for Configuration, Status, and
Diagnostics. (See the
HART Protocol
information)

Communications

The XNX
Universal Transmitter is registered with the HART
®
Communication Foundation. The transmitter
features HART over 4-20mA as standard.
Introduction
Description*
Notes
Fault
Warm-up
Special
Inhibit
State
Bump Test
Indication
Calibration
Warning
Overrange
section for additional
Additional optional communication interfaces are available:
relay communication, Modbus, or FOUNDATION Fieldbus.
Each communication option has a dedicated option board. For
additional information, refer to the
Certifications
XNX-UT**-****** Versions are UL and CSA listed for installation in
Class I, Division 1, Groups A, B, C and D Hazardous Locations.
FM Approvals evaluation includes Class I, Zone 1, Group IIC,
as well as performance tests for specific sensor/transmitter
combinations. The CSA or FM certification does not cover daisy-
chained XNX combustible gas transmitters, the use of HART,
Modbus, or FOUNDATION Fieldbus protocols for combustible
gas performance. HART, Modbus, or FOUNDATION Fieldbus
protocols can be used only for data collection or record keeping
with regards to combustible gas. The EC cartridge
remote mount kit are UL classified to Canandian and US
standards.
XNX-AM **-***** versions are certified to comply with the
European Community ATEX Directive and the prescribed
protection methods for installation in potentially explosive
atmospheres.
XNX-BT**-***** versions are UL listed and INMETRO approved for
compliance with both U.S. and Brazilian standards.
See the
Sensor Data
applicable approvals by part number and the
Storage Conditions for Performance Tested EC Sensors
for marking.
®
"Cartridge" and "sensor" are used interchangeably in this document.
2
12
Options
section.
section for additional information on
Operating and
and EC
2
section

Advertisement

Table of Contents
loading

Table of Contents