Settings - Honeywell XNX-AM Series Technical Manual

Hide thumbs Also See for XNX-AM Series:
Table of Contents

Advertisement

XNX Universal Transmitter
Table A
Board Type
Function
EC Personality
Source 
mV
Sink 
Personality
4-20mA
Output
IR
Isolated 
Personality
Table C
Board Type
Function
Source 
IR
IR 4-20mA
Personality
Input
Sink 
Table E
Board Type
Connection Function
Remote Reset
Relay
TB4
Connector
Bus Loop
Modbus
SW5
Terminators
Foundatin
SW5
Simulation Mode
Fieldbus
NOTE
!
Note: Open loop faults are not available due to HART, Modbus, and FOUNDATION Fieldbus
interfaces where a 4-20 signal cannot be used. In this case, open loop, 0mA must be
used as the diagnostic.
The Option circuit boards vary depending upon the option
selected when ordered. Only one of the three available interface
options (relays, Modbus, or FOUNDATION Fieldbus) can be
attached to the transmitter. When installed, connections to the
options are made to connectors at the bottom of the POD .
Installation and Operation
Table B
S1
S2
Board Type
Connection Function
EC Personality
mV Personality
TB1
IR Personality
Table D
S3
S4
Board Type
Connection Function
EC Personality
J2
IR Personality
TB2
Table F
Board Type
Connection Function
Relay
TB3
Modbus
TB3
Foundation
TB3
Fieldbus
4-20mA Output, Common Connections, and Power

Settings

Power, 4-20mA
Power, 4-20mA,
WARNING
!
Sensor
Power, 4-20mA,
IR Power and
Warning: Power off the transmitter before changing S3 or S4. Failure to do this will
Signal
permanently damage the transmitter. Both switches must be set in either Source or
Sink prior to applying power.
EC IS Barrier
The transmitter allows the user to configure the 4-20mA
Com A and B
output to Sink, Source, or Isolated mode operation via two
programming switches on the POD
table shows the S1 and S2 setting and corresponding output
configuration.
Relay Output
Data Connection
Data connection
Most controllers in the market will accept source-configured
devices. Sink-configured signals are used in older technology
controllers, which reduce the need for complete system
upgrades. In isolated-signal devices, if the controller fails or the
mA signal wires are disconnected or broken, the field device will
remain operational. Most controllers in the market will accept
isolated configured devices.
Power and 4-20mA connections are made at TB-1 and are
identical for the EC, IR, and mV Personality Boards. For user
convenience, a second set of +Ve and -Ve power terminals have
been provided to eliminate the need for a secondary junction
1 The 4-20 mA output state is refreshed at least every two seconds (once per second is typical).
39
. The Switch Configuration
1
Switch Configuration
Mode
S1
S2
Source
Down
Up
Sink
Up
Down
Isolated
Down
Down

Advertisement