XNX Universal Transmitter
NOTE
!
Note: Calibrated mA output is required for proper operation of internal diagnostics.
An F165 fault will be reported if the 4-20 mA calibration fails.

Align Excel (Searchline Excel)

Figure 221. Align Excel Menu
For detailed information on aligning the Searchline Excel, see
the Searchline Excel Technical Manual (Honeywell part number
2104M0506).
Signal Strength
Reference Value
1.00 Signal Strength Target
Figure 222. Align Excel Screen
Align the unit using the information found in the Searchline Excel
manual. As the alignment is performed, the transmitter display will
indicate the signal strength in the form of a bar graph. Align the
Excel until the signal strength bar graph reaches or exceeds 1.00 as
shown on the display.
Section 3 - Calibration
(Searchline Excel and Searchpoint Optima Plus only)
For transmitters connected to a Searchline Excel or Searchpoint
Optima Plus sensor, the Soft Reset sends these infrared devices a
signal to restart the sensor.
Alignment Bargraph
115
Soft Reset
Figure 223. Soft Reset Menu
Figure 224. Soft Reset Sensor Screen