Digital Output Wiring

Digital Output is available only on HART transmitters. The Digital Output should not
use the same power supply as used to support the 4-20mA transmitter output. See
Figure 14
and
Figure 15.
For Intrinsically Safe (IS) applications, the 4-20mA and the Digital Output must use
separate IS Barriers.

Figure 14: Digital Output Connections for mA Load (HART only)

For best performance, it is recommended that:
Digital Output wires should be in a separate shielded twisted pair cable,
do not use the same cable as used for the Loop or the Sensor wires
If using the same power supply to operate both the 4-20mA Loop and
the Digital Output, then make the interconnections to the power supply
terminals directly at the power supply
NOTE: Intrinsically Safe Installations require the use of separate IS Barriers
for the 4-20mA output and for the Digital Output connections

Figure 15: Digital Output Connections for PLC Counting Input (HART only)

14
Quick Start Installation Guide
SmartLine Temperature Transmitter