4 Configuration and project engineering
No.
Action
Additional settings can be made
under the "PROFIsafe" tab.
In STARTER, the value of
"F_Dest_Add" should be
entered in the hexadecimal
format for the drive.
"C6hex" or "198dec" were used
in this particular example.
4.
Note:
The watchdog time
("F_WD_Time" = 150msec)
should not be an integer multiple
of the OB 35 cycle. In the
example, the OB35 cycle is
100msec.
Close the screen form by
pressing the "OK" button.
Now save and compile the HW
5.
configuration.
Then load the HW Config to the
6.
target system.
42
Remark
PROFIsafe SLS Override