Troubleshooting

Troubleshooting
9. Troubleshooting

9.1 Error Code List

Error
Name of malfunction and
Code
status
CL
Filter cleaning reminder
Compressor RMS phase
d0
current limit down
RMS machine current
d1
limit down
Exhaust gas temperature
d2
limit down
d3
Anti-freeze limit down
d4
Overload limit down
d5
IPM temp limit down
High discharge temp
E0
protection
E1
Overload protection
Compressor overload
E2
protection
E3
Anti-freeze protection
E7
4 way valve malfunction
Outdoor ambient
E8
temperature abnormal
protection
H0
Compressor stalling
H1
Start up failure
52
Way of display
By remote control
By remote
procedure within
Display
conrol
compressor stop
directly
procedure
200s or direcly
only
after compressor
stop 200s
Error
Possible Causes
Type
Indoor Filter may have dust
Compressor phase current
effective value is too high,
Outdoor
the compressor need to limit
the frequency or frequency
reduction operation
The whole unit current
effective value is too high,
Outdoor
compressor need to limit
the frequency or frequency
reduction operation
The Exhaust pipe
temperature is too high,
Outdoor
compressor need to limit
the frequency or frequency
reduction operation
The inner pipe temperature
is too low, compressor
Outdoor
need to limit the frequency
or frequency reduction
operation
The system is overload,
compressor need to limit
Outdoor
the frequency or frequency
reduction operation
The compressor module
temperature is too high,
Outdoor
compressor need to limit
the frequency or frequency
reduction operation
Outdoor See Diagram 1
Outdoor See Diagram 2
Outdoor See Diagram 3
1. Indoor machine return air
is not smooth.
2. The fan speed is too low.
Outdoor
3. The fi lter or evaporator
not clean.
4. The inner temperature
sensor abnormal.
1.Supply voltage is unstable
2.Mainboard and 4-Way
Outdoor
valve unconnected.
3.4-Way valve is broken.
1. The outdoor environment
temperature is too high or
Outdoor
too low.
2. The outdoor environment
temprature sensor is damage.
Outdoor See Diagram 4
Outdoor See Diagram 5
Solution
Clean the fl iter
The normal limit frequency
reduction function.
The normal limit frequency
reduction function.
The normal limit frequency
reduction function.
The normal limit frequency
reduction function.
The normal limit frequency
reduction function.
The normal limit frequency
reduction function
See Diagram 1
See Diagram 2
See Diagram 3
1. Indoor machine return air
is not smooth.
2. The fan speed is too low.
3. The fi lter or evaporator
not clean.
4. Change the temperature
sensor abnormal.
1.Check the voltage of
power supply.
2.Check the connecting of
mainboard and 4-way valve.
3.Change the 4-Way valve.
1. The outdoor environment
temperature is in normal
range.
2. Change the temprature
sensor.
See Diagram 4
See Diagram 5