SPECIFICATIONS: ENGINEERING DATA TABLE
Model
Air System Data
Rated Air Flow at 100°F & 100 psig Inlet, 100°F Ambient (scfm)
Minimum / Maximum Inlet Compressed Air Pressure
Minimum / Maximum Inlet Compressed Air Temperature
Minimum / Maximum Ambient Temperature
Outlet Air Temperature (nominal at rated conditions)
Refrigeration System Data
Compressor Type
Refrigeration Compressor Horsepower
Refrigeration Capacity @ Rated Flow (BTU/hr)*
Refrigerant Type
Refrigerant Charge
Suction Pressure Setting
Compressor Pressure Switch Setting (cut out / cut in)
Air-Cooled Condensers
Air Flow Across Condenser (cfm)
Condenser Fan Switch Setting (cut in / cut out)
Water-Cooled Condensers
Water Regulating Valve Setting
Minimum Water Pressure Differential
Cooling Water Flow with 85°F (gpm)*
Electrical Data
Nominal Voltage
Voltage Range
Input Power @ Rated Flow (watts) *
Minimum Circuit Ampacity
Maximum Overcurrent Protector (amps)
Compressor Rated Load Amps
Compressor Locked Rotor Amps
NOTES
* 60 Hz: 35°F Evaporator & 100°F Ambient; 50 Hz: 35°F Evaporator & 77°F Ambient
MCGUIRE AIR COMPRESSORS INC
HGEN600
60 Hz
600
3 US RT
60 Hz
34,080
High, a-c
398 psig / manual reset (27.4 barg / manual reset)
High, w-c
313 psig / manual reset (21.6 barg / manual reset)
60 Hz
2,825
Fan 1 / Fan 2
60 Hz
6.15
3,800
7.8
15
5.7
30
1-888-229-9999
HGEN800
HGEN1000
800
1000
43.5 / 232 psig (3 / 16 barg)
45° / 120°F (7° / 49°C)
37° / 109°F (3° / 43°C)
86°F (30°C)
Hermetic Reciprocating
4 US RT
5 US RT
48,120
60,380
R-407C
See Data Tag on Dryer
60 psig (4.1 barg)
4,120
4,120
299 / 213 psig (20.6 / 14.7 barg)
220 psig (15.2 barg)
40 psig (2.8 barg)
8.19
10.24
460/3/60
414 - 506
5,400
6,600
10.1
12.6
20
20
7.3
9.4
42
67
1-888-229-9999
HGEN1200
1200
6 US RT
76,870
4,120
12.29
8,660
15.9
25
12.0
80