Siemens 7XV5662-0AB01 Directions For Use Manual page 68

Communication converter s0-bus with optical asynchronous input interface
Table of Contents

Advertisement

Available languages

Available languages

English
– Radiated Electromagnetic Interference
– Dampened oscillations
EMC tests for emitted interference
(Type test)
– Radio noise voltage to lines
– Radio noise field strength
– Voltage fluctuations
Vibration and shock stress
Shock stress on stationary deployment
– Vibration
– Shock
– Seismic vibration
Vibration and shock stress
During transport
– Vibration
– Shock
– Continuous shock
Temperatures
– Recommended temperature during
operation
– Permissible temporary (transient)
operating temperature
– Limit temperatures during storage
– Limit temperatures for operation
Storage and transport of the device with factory packaging!
Humidity
Admissible humidity conditions
All devices shall be installed so that they are not exposed to direct sunlight, nor subject to
great fluctuations in temperature that may cause condensation to occur.
68
ANSI/IEEE Std C37.90.2
IEC 60694, IEC 61000–4–12
EN 50081–1 (generic standard)
IEC–CISPR22 limit value B
IEC–CISPR 22 limit value Class B
IEC 61000–3–3
IEC 60255–21 and IEC 60068
IEC 60255–21–1, Class 1,IEC 60068–2–6
IEC 60255–21–2, Class 2, IEC 60068–2–27
IEC 60255–21–2, Class 2, IEC 60068–3–3
IEC 60255–21 and IEC 60068–2
IEC 60255–21–1, Class 2, IEC 60068–2–6
IEC 60255–21–2, Class 1, IEC 60068–2–27
IEC 60255–21–2, Class 1, IEC 60068–2–29
IEC 60068–2
–5 °C to +55 °C
–20 °C to +70 °C
–25 °C to +55 °C
–25 °C to +70 °C
yearly average ≤75 % relative humidity;
on 56 days per year up to 93 % relative
humidity;
during operation, condensation not
permissible!