Siemens 7XV5662-0AB01 Directions For Use Manual page 67

Communication converter s0-bus with optical asynchronous input interface
Table of Contents

Advertisement

Available languages

Available languages

7XV5662-0AB01
Interfaces to the CC–S
ISDN S
–Bus
0
– Connection
– Maximum transmission distance
– Transfer rate
– Test voltage
– Cable
Specifications
Standards:
Insulation tests:
EMC tests for interference immunity
(Type tests)
– High–frequency test
– Static electricity discharge
– Irradiation with HF field, unmodulated
– Irradiation with HF field, amplitude
modulated amplitude–modulated
– Irradiation with HF field, pulse
modulated pulse–modulated
– Fast transient interference
quantities/burst
– Energy–rich surge voltages
(SURGE)
– Line conducted HF, amplitude module.
– Magnetic field with electrical frequency
– Fast Transient Surge Withstand Capability
– Fast Transient Surge Withstand Capability
C53000-B1174-C166-1
0
5-pole screw terminal, potential–free
150 m (450 ft)
2 × (300 to max. 19.2 kbaud)
500 V; 50 Hz
5-pole data cable, screened
IEC 60255 (product standards)
DIN 57 435 part 303
ANSI/IEEE 37.90, 37.90.1, 37.90.2
IEC 60255–5 and IEC 60870–2–1
IEC 60255–6 and –22
(product standards)
EN 50082–2 (generic standard)
DIN 57 435 part 303
IEC 60255–22–1, Class III and
and VDE 0435 Part 303, Class III
IEC 60255–22–2, Class IV and
IEC 61000–4–2, Class IV
IEC 60255–22–3 (Report) Class III
IEC 61–4–3, Class III
IEC 61–4–3, Class III
IEC 60255–22–4 and IEC 61000–4–4,
Class IV
IEC 61000–4–5; Installation Class III
IEC 61000–4–6, Class III
IEC 61000–4–8, Class IV, IEC 60255–6
frequency
ANSI/IEEE C37.90.1
ANSI/IEEE C37.90.1
English