Power Supply - Fujitsu BS2000 SE Series Basic Operating Manual

Hide thumbs Also See for BS2000 SE Series:
Table of Contents

Advertisement

4.3 Power supply

The devices in the racks are supplied with power over power distribution units (PDUs).
SE /390
By default a basic rack contains four PDUs, each with 8 or 11 x C13 outlets.
Each PDU is connected to the in-house power grid with CEE connectors 32A resp. 16A (SE710) blue. For
redundancy reasons, two phases are required. Two of the four CEE connectors are connected to each phase.
SE x86
The power distribution units to be installed in the SE300 basic rack and in the extension racks can be selected. The
following three types of PDU can be installed:
PDU with 10 x C13 outlets, CEE connector 16A blue
3-phase PDU with 3 x 8 x C13 outlets, CEE connector 16A red
PDU with 8 x C13 outlets, CEE connector 32A blue
Connection of the power cables
Most of the hardware components in the SE server rack do not incorporate any switches which disconnect them
from the power source. Consequently the power cables of the hardware components must be attached or detached
when it is necessary to connect or disconnect the components from the power source.
Figure 11: Example of a power distribution unit as used in the rack
!
CAUTION!
Equipment damage
All work on the power supply must be conducted by Customer Support.
Connect each power cable to a grounded service outlet located within the operator's reach.
36

Advertisement

Table of Contents
loading

Table of Contents