EMS INTRODUCTION AND SET UP
Figure 55 Force Charge Start Time
Setting
Step 13 Set the charge start time
Figure 57 Charging cut SOC Setting
Step 15 Set the charging cut-off SOC.
Figure 59 Safety Setting Interface
Step 17 Click Safety in the setting
menu. Set safety standard.
ARN4105 for Germany, CEI0_21 for Italy,
G83_2 for Great Britain, AS4777 for
Australia
Figure 61 Ethernet interface
Figure 56 Force Charge End Time Setting
Step 14 Set the charging start time
Figure 58 Discharging cut SOC Setting
Step 16 Set the discharging cut-off SOC.
Figure 60 Date&Time Setting Interface
Step 18 Click System in the setting
menu. Click Date &Time and set up the
date and time.
Step 19 Click Ethernet to set the IP
address. DHCP mode means that setup IP
address is set up automatically.
If you want to set up the IP address
manually, please choose manual mode.
35
36
Note: It is needed to set the following 3 parameters for manual mode:
IP Address: IP address;
Subnet Mask: Subnet mask;
Default Gateway: Default gateway;
Automatic display one parameter:
MAC Address: display MAC Address.
Figure 62 Date&Time Setting Interface
Step 20 Click Language to set language

4.3 EMS Communication Checking

After wiring and EMS setting, check that the status indicators are normal. Then enter
MENU->Status->Communication to check that the communication status of all the
devices are normal.
AC\HYBRID system:
Figure 64 BMS
DC system:
Figure 66 BMS
EMS INTRODUCTION AND SET UP
Figure 63 Date&Time Setting Interface
Step 21 Make sure all the following
number is correct.
Figure 65 Ethernet and Meter
Figure 67 Ethernet and Meter