Siemens SIMATIC ET 200SP Manual page 26

Communication module io-link master cm 4xio-link (6es7137-6bd00-0ba0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space
4.3 Address space
Port configuration
With a IO-Link Master CM 4xIO-Link as of firmware version V2.2, you can commission the
IO-Link port of the IO-Link master and the connected IO-Link devices in two different ways:
● Port configuration without S7-PCT
● Port configuration with S7-PCT
Port configuration without S7-PCT
Requirements
You have activated the "Port configuration without S7-PCT" check box in the configuration of
the IO-Link master in STEP 7.
Procedure
You configure the IO-Link master directly in STEP 7:
● Activate the diagnostics
● Configuration of the I/O data lengths for each port
● Activate the PortQualifierInformation (PQI)
● Port mode:
– Operation in "IO-Link Autostart" mode (default)
– Operation in "IO-Link Manual" mode
– Operated as DI
– Operated as DQ
– Deactivated
Port configuration with S7-PCT
Requirements
You have deactivated the "Port configuration without S7-PCT" check box in the configuration
of the IO-Link master in STEP 7.
Procedure
You configure the IO-Link master with the Port Configuration Tool S7-PCT, V3.2 or higher.
26
Communication module IO-Link Master CM 4xIO-Link (6ES7137-6BD00-0BA0)
Manual, 10/2017, A5E03856846-AD