Siemens SIMATIC ET 200SP Manual page 24

Communication module io-link master cm 4xio-link (6es7137-6bd00-0ba0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space
4.2 Declaration of parameters
Operating mode
This parameter specifies in which mode the selected port is to be operated.
You can select from the following options:
● IO-Link Autostart
● IO-Link manual
● DI
● DQ
● Deactivated
IO-Link Autostart
The connected IO-Link device starts automatically (Plug&Play functionality). The IO-Link
device is immediately available to you and operational.
IO-Link manual
The connected IO-Link devices are not started automatically.
You must store the VendorID and DeviceID of the connected IO-Link devices in STEP 7.
In addition, you can select the test level for the data storage:
● Identical type (V1.0) without Backup&Restore
● Type-compatible (V1.1) without Backup&Restore
● Type-compatible (V1.1) with Backup&Restore
● Type-compatible (V1.1) with Restore
The VendorID and DeviceID can be found on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/109748852).
DI
The port operates as standard digital input.
DQ
The port operates as standard digital output.
Deactivated
The port is deactivated.
24
Communication module IO-Link Master CM 4xIO-Link (6ES7137-6BD00-0BA0)
Manual, 10/2017, A5E03856846-AD