Batch controller two-stage control and pulse output, signal input flowmeter: pulse, namur and coil, external controls: start and stop, digital outputs: two control outputs for two stage control, or one control output and pulse output, options: intrinsical (48 pages)
Batch controller with two-stage control, analog and pulse outputs signal input flowmeter: pulse, namur and coil external controls: start and stop digital outputs: two control outputs for two stage control, or one control output and pulse output ref. total (53 pages)
Ratio controller, signal input flowmeter: pulse, namur and coil, control output: 0 4-20ma/0-10v, alarm outputs: high/low ratio alarm, options: intrinsically safe, modbus communication and backlight (48 pages)
Batch-controller with receipt printer driver, signal input flowmeter type p: pulse, namur and coil, status inputs: start and stop, control output: two control outputs for one- and two-stage control, communication: printer interface for receipt printing, o (40 pages)
Summary of Contents for Fluidwell N-410-P
Page 1
Signal input flowmeter: Pulse – Coil, NPN, PNP, Reed, Namur, Active Control input: Five inputs for remote control. Control output: Three outputs to control valves, pumps and alarms Communication: Modbus RTU/ASCII Save time and cost with the user-friendly N410 batch controller. More info: www.fluidwell.com/nseries...
Page 3 DISCLAIMER • The information contained in this document is subject to change without notice. The manufacturer makes no representations or warranties with respect to the contents hereof and specifically disclaim any implied warranties of merchantability or fitness for a particular purpose. •...
▪ appointed for the certification, the occupational, health, safety and the quality tasks. WARRANTY AND TECHNICAL SUPPORT For warranty and technical support for your Fluidwell products, visit our internet site www.fluidwell.com or contact us at support@fluidwell.com.
Page 7 INTRODUCTION 1.1. SYSTEM DESCRIPTION OF THE N410-P Functions and features The batch controller model N410-P is a microprocessor driven instrument designed for batching and filling of small and large batch size quantities. This product has been designed with a focus on: ▪...
Page 8
Page 8 Control outputs ▪ Two mechanic relay outputs are mainly used for one or two-stage batch control processes. The function of the relay R1 (SPDT) is fixed and is set for batch control (Batch). In most applications, this relay is used as the main batch control relay. The function of the relay R2 (SPDT) is configurable in the setup menu and can be set as batch relay (Batch) or as an output for two-stage control (Preclose), or as an alarm output (Alarm), or as a scaled pulse output (Pulse).
Page 9
Page 9 Display information The unit has a large LCD with a bright LED backlight and displays all kinds of symbols, digits and measuring units, status information and key-word messages. P R O G S T A R T E N T ER H O L D R E S E T R AT E...
Page 10 OPERATIONAL 2.1. GENERAL ▪ The N410-P may only be operated by authorized and trained personnel. ▪ All instructions in this manual are to be observed. ▪ Take careful notice of the "Safety rules, instructions and precautionary measures" in the front of this manual.
Page 11 2.3. OPERATOR INFORMATION AND FUNCTIONS In general, the N410-P will always function at Operator level. The information displayed and the functional keys available are dependent upon the SETUP-settings and the active function. NOTE: If the key-sign is displayed, FW-4100-000014-001-EN the particular key(s) or functions are not accessible! ▪...
Page 12
Page 12 ▪ Interrupting and ending the batch process 1. Press HOLD: Interrupts the batch process temporarily, the pump stays on and the actual data is kept while the display shows HOLD (flashing). 2. Press HOLD, START, The interrupted batch is resumed. Press HOLD, RESET: Stops the batch process at any time, the batch sequence is ended as a completed batch and the remaining quantity of the batch is ignored.
Page 13 OPERATOR ALARMS ▪ General alarm When “ALARM” is displayed when no process alarm is present (e.g. no flow, press the “1” key to display the reason of the alarm. Please consult Appendix B: Problem Solving. ▪ No flow alarm The N410-P offers a no-flow monitoring feature: if the flowmeter fails to generate a signal during a certain period of time, the unit will shut-off the control output(s) and bring the batch controller in HOLD and alarm mode: an alarm message will be displayed, indicating the type...
Page 14 INSTALLATION 3.1. GENERAL DIRECTIONS • Installation, electrical wiring, start-up and maintenance of this instrument may only be carried out by authorized and trained personnel. Personnel must read and understand this Instruction Manual before carrying out any work. • The N410-P may only be operated by personnel who are authorized and trained by the operator of the facility.
Page 15 3.2.2. INSTALLATION / SURROUNDING CONDITIONS Take the relevant IP classification of the enclosure into account (see manufactures plate). Even with an IP67 (Type 4X) enclosure, the unit should not be exposed to harsh unnecessary harsh weather conditions. When used in extreme cold surroundings or varying climatic conditions, take the necessary precautions against moisture by placing a dry sachet of silica gel, for example, inside the control cabinet.
Page 16 3.2.4. INSTALL THE UNIT INTO THE CABINET (PANEL) 1. Install the screws in the clamps (1, 3, 4, 7). 2. Install the gasket onto the unit (2). 3. Put the unit (2) in the correct position for installation. 4.
Page 17 Cable and wire selection The unit complies with the Directives and Standards for Electro Magnetic Interference. For a reliable signal transfer and prevention of external signal interference (crosstalk), for signal wiring, the recommendation is made for a shielded (twisted pair) cable which meets at least the Category 5 cable standard.
Page 18
Page 18 Sine-wave signal (Coil): The N410-P can be connected to flowmeters that have a coil output signal. With SETUP 6.1 two sensitivity levels can be selected: • COIL LO: sensitivity from about 120mVp-p. • COIL HI: sensitivity from about 20mVp-p Figure 13: Terminal connections - Coil signal input (typical) Reed-switch: The N410-P is suitable for use with flowmeters which have a reed-switch.
Page 19
Page 19 Pulse-signal NPN / NPN LP: The N410-P is suitable for use with sensors which have a NPN output signal. For reliable pulse detection, the pulse amplitude has to go above 1.2V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input frequency - read par. 4.2.8. Figure 16: Terminal connections - NPN signal input (typical) Active signal: If a sensor gives an active signal (read chapter 3).
Page 20
Page 20 Terminal 8 - 9; External control - Start With this function, the batch controller can be STARTED remotely. The input must be switched with a potential free contact to the GND-terminal number 8 for at least 100msec. Figure 19: Terminal connections - External start (typical) Terminal 8-10;...
Page 21
Page 21 Terminal 8-12; External Alarm: With this function an external alarm release can be connected to the N410-P. A running batch will be interrupted immediately and will be blocked till the alarm status is initialized. Initialization is only accepted if the input is released. Initialization can be done by pressing the RESET button or by switching terminal 11 (EXTERNAL RESET) to terminal 8.
Page 22
Page 22 Terminal 27-28; 24V DC Power Supply: Use these terminals ONLY for DC operated applications. The supply must be a 24V DC +10%. For AC applications, use terminals 22-24. Terminal 35 to 37: Type CB / CH - RS232/485 (2-wire) communication (optional) : ▪...
Page 23 CONFIGURATION 4.1. INTRODUCTION This and the following chapters are exclusively for electricians and non-operators. In these, an extensive description of all software settings and hardware connections are provided. ▪ Installation, electrical wiring, start-up and maintenance of the instrument may only be performed by authorized and trained personnel.
Page 24
Page 24 SCROLLING THROUGH SETUP-LEVEL Selection of function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number. The number is a combination of two figures. The first figure indicates the function-group and the second figure the sub-function. Additionally, each function is expressed with a keyword.
Page 26 4.2.3. EXPLANATION OF SETUP 1 - PRESET UNIT This setting is used to select the engineering unit for the indication of the batch total, the accumulated total and the pulse output. Alteration of the measuring unit will have consequences for operator and SETUP menu values.
Page 27 CUT-OFF With the cut-off time, you determine a minimum flow requirement thresh- hold, if during this time less than XXX-pulses (SETUP 3.4) are generated; the flowrate will be displayed as zero. The cut-off time must be entered in seconds - maximum time is 999.9 seconds (approx.
Page 28 cubic feet. The more accurate the K-factor, the more accurate the functioning of the system will be. Example 1: Calculating the K-factor. The flowmeter generates 2.4813 pulses per liter and the selected unit is m cubic meter consists of 1000 liter which gives 2.4813 pulses*1000 liter=2481.3 pulses per m .
Page 29 4.2.10. EXPLANATION OF SETUP 8 - COMMUNICATION The functions described below relates to communication with an external device. For communication variables: read Appendix C – communication. SPEED For external control, the following communication speeds can be selected: 1200 – 2400 – 4800 – 9600 – 9600HP – 19200 – 38400 ADDRESS For communication purposes, a unique identity can be attributed to every N410-P.
(ANSI/NEDA 5020LC/AWCI L09), Lithium-Carbon/Fluoride, 3V/48mAh, Low-drain. 5.3. REPAIR POLICY If you have any problem with your Fluidwell product and you wish Fluidwell to repair it, please follow the procedure below: a. Obtain a Return Material Authorization (RMA) from your supplier or distributor Together with the RMA, you need to complete a repair form to submit detailed information about the problem.
Page 31 APPENDIX A: TECHNICAL SPECIFICATION General Display Type High intensity numeric and alphanumeric LCD, UV-resistant. White LED backlight. Intensity adjustable form 0 – 100% in steps of 20%. Good readings in full sunlight and darkness. Dimensions 22 x 116mm (0.87 x 4.57”). Digits Seven 14mm (0.56”) and ten 8mm (0.3”).
Page 32
Page 32 Outputs Control outputs Function One batch output (always a mechanical relay). Two configurable outputs (one mechanical relay and one transistors: batch / two-stage control / any alarm / scaled pulse outputs. Scaled pulse output Max. Frequency 500Hz. Pulse width is user definable between 1msec up to 10 seconds. Mechanical relays 2 isolated, field replaceable, electro-mechanical relays (NO-NC).
Page 33 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the N410-P is going to be installed or while it is in operation. N410-P will not switch on, seems to have no power: Fuse blown ▪...
0x0000.0002.6CD0 = 158928. If this value needs to be calculated: 0*65536*65536 + 2*65536 + 27856 = 158928. For additional information regarding using your Fluidwell Modbus device, please read the ‘Fluidwell General Modbus Communication Protocol’ and ‘Modbus troubleshooting guide’ that are available through our website or your distributor.
Page 35
Page 35 Preset variables REGISTER VARIABLE TYPE VALUE / REMARKS ADDRESS REGISTERS d: 108 40033 unit uint16 0=L 3= I GAL 6=kg 9=lb h: 0x06C 4=FT3 7= ton 1= m 5= BBL 8=US ton 2=US GAL d: 33 40034 decimals uint16 0…3 h: 0x021 d: 214...
Page 38 INDEX OF THIS MANUAL accumulated Total k-factor actual settings maintenance alarm model backlight no-flow alarm density Operator level Batch counter Passcode batch maximum power supply 21, 22 Batch maximum Preclose/two stage Cabinet installation preset Clear Total max. batch size Coil-signal Preset Communication...
Page 39
Page 39 LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE : DATE : 1. – PRESET Enter your settings here 1.1 unit 1.2 decimals 0000000 1.3 minimum batch 1.4 maximum batch 1.5 preset 2. – OVERRUN 2.1 overrun disabled 2.2 time 1.0 sec 3.
Page 40