Toshiba TOSNIC-7000S Instruction Manual page 31

Toshiba uninterruptible power system instruction manual
Table of Contents

Advertisement

Step
Procedure
10
Hold down the "UPS"
key (
in the Figure
6.3.1 on page14) for at
least 0.5 second. *
→ The will start the
power supply
changing process.
11
Wait several seconds
for the process to be
completed (change to
UPS power supply).
→This completes the
UPS staartup
operation.
*If for some reason the AC switch dose not function, contact the Toshiba Service Center.
Do not manually operate the solenoid contactor (which is part of AC switch).
Table 8.1
Startup Procedures (continued)
LCD/LED Status (After Execution)
UPS SUPPLY
AC INPUT
CONVERTER
FLOAT CHARGE
BATTERIES
EQUAL CHARGE
DISCHARGE
BYPASS INPUT
The "BYPASS" LED unlit and "UPS" LED lit.
UPS SUPPLY
AC INPUT
CONVERTER
FLOAT CHARGE
BATTERIES
EQUAL CHARGE
DISCHARGE
BYPASS INPUT
- 30 -
6 F 3 H 1 0 0 1