Step
Procedure
8
Turn off the precharge
circuit switch (6CH).
9
Wait about 20 minutes
until the DC capacitor
has been discharge.*
10
Using the scroll keys,
change the display
screen and check to
make sure that the DC
voltage is 0V (see
Section 7.2.4 "LCD
Screen Switching" on
page 24).
11
Set the control power
supply switch (8A) to
the OFF position. *
→ Complete shutdown
*
This operation is different from that displayed in the help message on the screen.
Be sure to perform the operation as described here.
Table 8.4
Complete Shutdown (continued)
LCD/LED Status (After Execution)
OPERATION GUIDANCE
MOVE #6CH TO 'OFF' POSITION
WAIT ABOUT 20 MINUTES
MOVE #8A TO 'OFF' POSITION
AC INPUT
CONVERTER
FLOAT CHARGE
BATTERIES
EQUAL CHARGE
DISCHARGE
BYPASS INPUT
OPERATION GUIDANCE
MOVE #6CH TO 'OFF' POSITION
WAIT ABOUT 20 MINUTES
MOVE #8A TO 'OFF' POSITION
DC INPUT
Nothing at all is displayed on the LCD and all LEDs are
unlit.
- 36 -
6 F 3 H 1 0 0 1
UPS
INVERTER
AC
SWITCH
BYPASS
DC-V
0[V]
BATT-V
0[V]
BATT- I
0[A]
AC OUTPUT