Wiring Method; Wiring Details - Honeywell CVL4022ASVAV1 Engineering Manual

Stryker lon vav system
Table of Contents

Advertisement

Wiring Method

NOTE: When attaching two or more wires to the same
terminal, other than 14 AWG (2.0 sq mm), be sure to twist
them together. Deviation from this rule can result in improper
electrical contact (see Fig. 17). Each terminal can
accommodate the following gauges of wire:
• Single wire: from 22 AWG to 14 AWG solid or stranded
• Multiple wires: up to two 18 AWG stranded, with 1/4 watt
wire-wound resistor
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the
required terminal location and tighten the screw.
3. If two or more wires are being inserted into one terminal
location, twist the wires together a minimum of three turns
before inserting them (see Fig. 17).
4. Cut the twisted end of the wires to 3/16 in. (5 mm) before
inserting them into the terminal and tightening the screw.
5. Pull on each wire in all terminals to check for good
mechanical connection.
1.
STRIP 1/2 IN. (13 MM)
1/2
FROM WIRES TO
(13)
BE ATTACHED AT
ONE TERMINAL.
2.
TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3.
Fig. 17. Attaching two or more wires at terminal blocks.
31-00083—02
CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM)
BEFORE INSERTING INTO TERMINAL AND
TIGHTENING SCREW. THEN PULL ON EACH
WIRE IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.

Wiring Details

Each controller is shipped with the digital outputs, which
switch the 24 Vac to the load (High Side). The three analog
outputs (AO) are used to control modulating heating, cooling
and economizer equipment. Any AO may be used as a digital
output, as follows:
• False (0%) produces 0 Vdc, (0 mA)
• True (100%) produces the maximum 11 Vdc (22 mA)
The wiring connection terminals described in Table 10 are
shown in Fig. 19 and Fig. 20 on page 20 and 20.
Table 10. Description of wiring terminal connections.
Terminal
1
24 Vac
2
24 Vac COM
3
EGND
4
20Vdc
5
SBUS 1
6
SBUS 2
7
NET-1
8
NET-2
9
DO-3
10
COM
11
DO-4
12
COM
13
DO-1
14
DO-2
15
COM
16
AO-1
17
COM
18
AO-2
19
UI-1
20
COM
21
UI-2
22
UI-3
23
COM
24
UI-4
a
For the CVL4022AS controller ONLY, terminals 9-12 (DO3, DO4, &
M17207A
COM) are not present. The actuator is internally hardwired to these ter-
minals.
b
Analog outputs may be configured as digital outputs and operate as
follows:
– False (0%) produces 0 Vdc, (0 mA)
– True (100%) produces the maximum 11 Vdc (22 mA)
18
Label
Connection
INPUT POWER & GROUND
24 Vac Power
24 Vac Power
Earth Ground
20 Vdc Power
Sylk
Sylk
NETWORK CONNECTIONS
L
W
® communications
ON
ORKS
L
W
® communications
ON
ORKS
a
DIGITAL OUTPUTS
Digital Output
Common
Digital Output
Common
Digital Output
Digital Output
Common
b
ANALOG OUTPUTS
Analog Output
Common
Analog Output
UNIVERSAL INPUTS
Universal Input
Common
Universal Input
Universal Input
Common
Universal Input