Honeywell CVL4022ASVAV1 Engineering Manual page 82

Stryker lon vav system
Table of Contents

Advertisement

Nv/field
nvoReheatPos
nvoReheatStgs
nvoSbusSensors
ZioTemp
ZioRh
C7400Temp
C7400Rh
nvoSensorOcc
nvoShare
31-00083—02
Table 22. Network Variable - Outputs (Continued)
Net Data Type
SNVT_
Reheat commanded control position.
lev_percent
-163%
range
count
Number of active heating coil stages.
0
range
SNVT
Calibrated Zio wall module temperature value.
temp_p
Output = SbusValue + nciWallModZio.TempOffset
30
range
SNVT_
Calibrated Zio wall module RH value
lev_percent
Output = SbusValue + nciWallModZio.RhOffset
0
range
SNVT
Calibrated C7400s temperature value
temp_p
Output = SbusValue + nciSbusSnsr.TempOffset
-40
range
SNVT_
Calibrated C7400s RH value
lev_percent
Output = SbusValue + nciSbusSnsr.RhOffset
0
range
SNVT
OccSensorOut is an output showing the current state of the hard wired occupancy
occupancy
sensor. The valid enumerated states are listed below:
State
0 Occ
1 UnOCC The space is not occupied
255 Null
In some cases a sending node(master VAV controller) with a wall module may be
used to control the Damper, ReHeat and Peripheral heat of one or more other
receiving nodes (satellite VAV controllers) that do not have a wall module. To use
this feature:
All nodes involved must be configured to have the same kind of ReHeat via
ReHeatType.
The satellite receiving nodes must have FlowControlType set to ShareWallModule.
The satellite receiving nodes must have nviShare bound to nvoShare of a node
having a wall module.
Description
163%
3
110F
100%
150F
100%
Meaning
The space is occupied
The occupancy sensor is not configured
82