DETAILED LIST OF NVS/POINTS
This section lists all the Lon network variables available in the
controller.

Input Configurations

NCI/Field
Net Data Type
nciUI1
type
ubyte
nciUI2
type
ubyte
nciUI3
type
ubyte
Table 15. Local Input Configuration
AP Internal
Default Val
Units
13
13
13
39
Description
Local Universal Input Configuration
Universal input type
0: 20 Kntc (UI_20Kntc)
1: TR2x 20Kntc (UI_TR2xSensor)
2: TR2x SetPt Absolute(UI_TR2xSetPtAbs)
3: TR2x SetPt Relative (UI_TR2xSetPtRel)
4: RH 0 to 10 vdc (UI_RH_0_10vdc)
5: RH 2 to 10 vdc (UI_RH_2_10vdc)
6: CO2 0 to 2000 ppm (UI_CO2)
7: Press 0 to 5 inWc (UI_Press5inWc)
8: Press 0 to 2.5 inWc (UI_Press2_5inWc)
9: Press 0 to 0.25 inWc (UI_PressQtrInWc)
10: Voltage Sensor 0 to 10 vdc (UI_Volt)
11: Custom Sensor 1 (UI_Custom1)
12: Custom Sensor 2 (UI_Custom2)
13: Digital Normally Open (UI_DI_NO)
14: Digital Normally Closed (UI_DI_NC)
Local Universal Input Configuration
Universal input type
0: 20 Kntc (UI_20Kntc)
1: TR2x 20Kntc (UI_TR2xSensor)
2: TR2x SetPt Absolute (UI_TR2xSetPtAbs)
3: TR2x SetPt Relative (UI_TR2xSetPtRel)
4: RH 0 to 10 vdc (UI_RH_0_10vdc)
5: RH 2 to 10 vdc (UI_RH_2_10vdc)
6: CO2 0 to 2000 ppm (UI_CO2)
7: Press 0 to 5 inWc (UI_Press5inWc)
8: Press 0 to 2.5 inWc (UI_Press2_5inWc)
9: Press 0 to 0.25 inWc (UI_PressQtrInWc)
10: Voltage Sensor 0 to 10 vdc (UI_Volt)
11: Custom Sensor 1 (UI_Custom1)
12: Custom Sensor 2 (UI_Custom2)
13: Digital Normally Open (UI_DI_NO)
14: Digital Normally Closed (UI_DI_NC)
Local Universal Input Configuration
Universal input type
0: 20 Kntc (UI_20Kntc)
1: TR2x 20Kntc (UI_TR2xSensor)
2: TR2x SetPt Absolute (UI_TR2xSetPtAbs)
3: TR2x SetPt Relative (UI_TR2xSetPtRel)
4: RH 0 to 10 vdc (UI_RH_0_10vdc)
5: RH 2 to 10 vdc (UI_RH_2_10vdc)
6: CO2 0 to 2000 ppm (UI_CO2)
7: Press 0 to 5 inWc (UI_Press5inWc)
8: Press 0 to 2.5 inWc (UI_Press2_5inWc)
9: Press 0 to 0.25 inWc (UI_PressQtrInWc)
10: Voltage Sensor 0 to 10 vdc (UI_Volt)
11: Custom Sensor 1 (UI_Custom1)
12: Custom Sensor 2 (UI_Custom2)
13: Digital Normally Open (UI_DI_NO)
14: Digital Normally Closed (UI_DI_NC)