Honeywell CVL4022ASVAV1 Engineering Manual page 78

Stryker lon vav system
Table of Contents

Advertisement

Nv/field
Mode
EffectOcc
OverRide
SchedOcc
NetManOcc
SenOcc
31-00083—02
Table 22. Network Variable - Outputs (Continued)
Net Data Type
ubyte
Indicates the current mode of the node determined by many inputs and arbitrated by
control logic.
0 - Startup wait
1 - Heat
2 - Cool
3 - Reheat
4 – Morn_Warm
5 – Night Purge
6 – Pressurize
7 – Depressurize
8 – Trackflow
9 – Manual Damper Position
10 – Manual Flow
11 - Freeze Protect
12 – Factory Test.
Not supported Note 1
13 – IO Test
Not Supported. Note 1
14 – Float out sync
Not Supported.
15 – Disabled
Not Supported. Note 1
16 – Manual
Not Supported. Note 1
17 – Emerg Command Purge
18 – Emerg Command Shutdown
19 – Htg and Clg Disabled.
20 – Fan only
Notes:
1. Refer to nvoNodeStatus.manual_control
SNVT
Effective occupancy
occupancy
0: Occupied
1: Unoccupied
2: Bypass
3: Standby
SNVT
Effective manual override state. The result of arbitration of inputs from: Network Man
occupancy
Occ and the Wall Module bypass signal.
0: Occupied
1: Unoccupied
2: Bypass
3: Standby
SNVT
Scheduled occupancy state.
occupancy
0: Occupied
1: Unoccupied
3: Standby
255: Null
SNVT
Reports the network manual occupancy state from nviManOcc.
occupancy
0: Occupied
1: Unoccupied
2: Bypass
3: Standby
255: null
SNVT
Indicates the current state of the sensed occupancy
occupancy
Output
0 Oc
1 UnOcc1
255 Null
Description
Meaning
The space is occupied
The space is not occupied
The occupancy sensor is not configured
78