Honeywell CVL4022ASVAV1 Engineering Manual page 95

Stryker lon vav system
Table of Contents

Advertisement

NCI/Field
nciPwrUpDisable
nciRecovClg
MaxClRmp
MinClRmp
OTMxClRmp
OTMnClRmp
nciRecovHtg
MaxHtRmp
MinHtRmp
OTMxHtRmp
OTMnHtRmp
nciSpSpcFrz
nciSpcTempAlm
HiLimit
LoLimit
Delay
Table 23. Configuration Parameters (Continued)
AP
Net Data
Default
Internal
Type
Val
Units
SNVT
10
sec
time_sec
∆F/hr
6
∆F/hr
2
∆F/hr
∆F/hr
SNVT
70
F
temp_p
SNVT
90
F
temp_p
∆F/hr
8
∆F/hr
2
∆F/hr
∆F/hr
SNVT
60
F
temp_p
SNVT
0
F
temp_p
SNVT
46.4
F
temp_p
SNVT
90
F
temp_p
SNVT_
50
F
temp_p
SNVT_
1800
sec
time_min
Controller power up disable time. Local logical digital outputs are
disabled for a fixed time at power up. Emergency mode bypasses
the power up disable.
1
range
300 sec
Precision: 0
Max cooling setpoint ramp
0
range
36 ∆F/hr
Precision: 3
Min cooling setpoint ramp
Cooling recovery rate when an outdoor air temperature sensor
value is not available.
0
range
36 ∆F/hr
Precision: 3
Outdoor air temperature at the max cooling ramp
-30
range
120 F
Precision: 1
Outdoor air temperature at the min cooling ramp
-30
range
120 F
Precision: 1
Max heating setpoint ramp
0
range
36 ∆F/hr
Precision: 3
Min heating setpoint ramp.
Heating recovery rate when an outdoor air temperature sensor
value is not available.
0
range
36 ∆F/hr
Precision: 3
Outdoor air temperature at the max heating ramp
-30
range
120 F
Precision: 1
Outdoor air temperature at the min heating ramp
-30
range
120 F
Precision: 1
Space freeze protection setpoint.
The space heating setpoint is shifted to this value when a window
is opened.
-30
range
70 F
Precision: 1
Space temperature occupied alarm high limit
LoLimit < range ≤ 100F
Precision: 1
Space Temperature occupied alarm low limit
40F ≤ range < HiLimit
Precision: 1
Space Temp alarm disable delay from a change to occupied.
0
range
32767 sec
Precision: 0
95
Description
31-00083—02