Nv/field
fan_output
in_alarm
nvoVelSenPress
nvoWindow
aka
nvoEnergyHoldOff
Table 22. Network Variable - Outputs (Continued)
Net Data Type
If a fan is configured as one speed, This value is 100 percent, when the fan is
running and is zero when the fan is not running. If a modulating fan is configured,
reports the fan speed in percentage.
0 – 100%
0 - Means there is no application alarm.
Not 0 - Means there is an application alarm
SNVT
The calibrated value of the cooling airflow pressure sensor. The sensor value minus
press_f
the offset value.
-0.0494
This network output allows the hard wired window sensor to be used by other
SNVT
switch
nodes on the network.
The valid states are described below:
State
SW_OFF
SW_ON
SW_NUL
Description
range
1.5833 inWc
Value
0
Window closed
100%
Window open
0
Window sensor not configured
85
Meaning
31-00083—02