Honeywell CVL4022ASVAV1 Engineering Manual page 66

Stryker lon vav system
Table of Contents

Advertisement

Net Data
NCI/Field
FreePlsOff
ReheatMod
ClgDmpr
31-00083—02
Table 20. Logical Output Configuration (Continued)
Default
Type
Val
ubyte
255
Free digital pulse OFF output. Typically connected to a lighting relay. The output
is controlled from the network command through nviFree1Dig.
Output Type: Binary
Default: Undefined
0
range
0
1
2
3
4
5
255 Undefined
ubyte
255
Reheat modulating output.
Output Type: PWM, Float, Analog Current or Voltage
Default: AO1
0
range
0
1
2
3
4
5
6
7
255 Undefined
ubyte
6
Cooling damper modulating output
Output Type: PWM, Float, Analog Current or Voltage
Default: Float1
0
range
0
1
2
3
4
5
6
7
255 Undefined
Description
255
AO1in
AO2in
DO1in
DO2in
DO3in
DO4in
255
AO1in
AO2in
DO1in
DO2in
DO3in
DO4in
Float1in
Float2in
255
AO1in
AO2in
DO1in
DO2in
DO3in
DO4in
Float1in
Float2in