NCI/Field
Net Data Type
nciFloat1
action
travelTime
time_sec
autoSync
syncIntvl
time_hour
pwrUpSync
pwrUpDelay
time_sec
UnOccSync
NviSync
Table 18. Local Output Configuration (Continued)
Default Val
ubyte
0
SNVT_
90
ubyte
0
SNVT_
24
ubyte
0
SNVT_
0
ubyte
0
ubyte
0
Configure floating output
Pin1 = DO3 (DO must be configured binary, nciDO3.type =
0)
Pin2 = DO4 (DO must be configured binary, nciDO4.type =
0)
Note:
To free up binary outputs DO3 & DO4, set the travelTime = 0
Reverse action
0: False 100%=full open, 0% = full closed
1: True 100%=full closed, 0% = full open
Motor travel time
0 ≤
≤ 3276.7 sec
range
Precision: 1
Notes:
Set the travel time to zero to disable the Floating Output and
free up DO3 & DO4
Auto Sync Type
0: none
1: Sync closed
2: Sync open
Refer to Appendix E – Floating Actuator Auto Synch
Auto sync interval
0 ≤
≤ 254 hours
range
Precision: 1
Power up Sync Type
0: none
1: Sync closed
2: Sync open
Refer to Appendix E – Floating Actuator Auto Synch
Actuator Power up delay.
0 ≤
≤ 3276.7 sec
range
Precision: 1
Sync the floating actuator on an occupancy transition to
unoccupied.
0: none
1: Sync closed
2: Sync open
Sync the floating actuator on an active nviFree1Dig signal.
0: none
1: Sync closed
2: Sync open
57