Actuator controls
AC 01.2/ACExC 01.2 Foundation Fieldbus
CHANNEL parameter
Ch DITB not ready REMOTE
1 [8 bit]
Ch DITB not ready REMOTE
2 [8 bit]
Ch DITB fault 1 [8 bit]
Ch DITB fault 2 [8 bit]
Ch DITB warnings 1 [8 bit]
Ch DITB warnings 2 [8 bit]
Value
Used Trans-
ducer Block
28
DITB
29
DITB
30
DITB
31
DITB
32
DITB
33
DITB
Explanation
Not ready REMOTE 1
Bit 0: Wrong oper. cmd
Bit 1: Sel. sw. not REMOTE
Bit 2: Interlock active
Bit 3: Local STOP
Bit 4: EMCY STOP act.
Bit 5: EMCY behav. active
Bit 6: FailState fieldbus
Bit 7: I/O interface
Not ready REMOTE 2
Bit 0.1: -
Bit 2: SIL function active
Bit 3: Disabled
Bit 4: Interlock by-pass
Bit 5: PVST active
Bit 6: Service active
Bit 7: Handwheel active
Fault 1
Bit 0: Configuration error
Bit 1: Mains quality
Bit 2: Thermal fault
Bit 3: Phase failure
Bit 4: Torque fault OPEN
Bit 5: Torque fault CLOSE
Bit 6: Internal error
Bit 7: No reaction
Fault 2
Bit 0-5: -
Bit 6: Config. error REMOTE
Bit 7: Incorrect phase seq
Warnings 1
Bit 0-3: -
Bit 4: Torque wrn CLOSE
Bit 5: Torque wrn OPEN
Bit 6: SIL fault
Bit 7: Wrn no reaction
Warnings 2
Bit 0: Wrn controls temp.
Bit 1.2: -
Bit 3: 24 VDC external
Bit 4: -
Bit 5: RTC button cell
Bit 6: RTC not set
Bit 7: Config. warning
Commissioning
37