Short instructions
FO connection

Advertisement

Table of Contents
loading

Summary of Contents for AUMA AUMATIC ACExC

  • Page 1 Actuator controls AUMATIC ACExC 01.2 Profibus DP To be used in combination with the operation instructions only! The present short instructions do NOT replace the operation instructions! They are only intended for persons already familiar with the operation instructions where safety instructions, assembly, operation and commissioning are already descr ibed in detail! The operation instructions must always be available.
  • Page 2: Table Of Contents

    Table of contents Table of contents Page Short description........................FO connection........................2.1. Basic information 2.2. Terminal compartment: open 2.3. FO cables: connect 2.4. Terminal compartment: close Network topologies........................ 3.1. Line topology 3.2. Star topology 3.3. Ring topology (two-fibre ring) Corrective action........................4.1.
  • Page 3: Short Description

    Short description Short description AUMA actuator controls with FO connection are intended for use in optical fieldbus networks. The FO connection integrated in the electrical connection enables the conversion from electrical RS-485 signals into optical signals and vice versa. FO connection behaviour is transparent at the bus, i.e. control of AUMA actuators via bus is identical to control via copper cables (RS-485).
  • Page 4: Fo Connection

    FO connection FO connection Basic information Hazardous voltage! Risk of electric shock. Failure to observe this warning can result in death or serious injury. The connection must be carried out exclusively by suitably qualified personnel. Prior to opening: Disconnect both system and device from the mains. Observe basic information contained in this chapter.
  • Page 5: Terminal Compartment: Open

    FO connection Terminal compartment: open Figure 2: Plug/socket connector: left KES, right KES flameproof Cover Screws for cover O-ring Terminal compartment: Type of protection Ex e Terminal compartment: Type of protection Ex d Frame Hazardous voltage! Risk of electric shock. Disconnect device from the mains before opening.
  • Page 6: Fo Cables: Connect

    FO connection FO cables: connect Remove safety circlip and take FO coupler off top head rail. Figure 3: FO coupler on top head rail Place FO coupler on fixing plate in "parking position" Figure 4: FO coupler in "parking position" Insert FO cables through cable glands.
  • Page 7: Terminal Compartment: Close

    FO connection Terminal compartment: close Figure 6: Plug/socket connector: left KES, right KES flameproof Cover Screws for cover O-ring Terminal compartment: Type of protection Ex e Terminal compartment: Type of protection Ex d Frame Clean sealing faces of cover [1] and housing. Plug/socket connector designed as KES flameproof: Preserve joint surfaces with an acid-free corrosion protection agent.
  • Page 8: Network Topologies

    Network topologies Network topologies When connecting several field devices (actuators) in a network, the structure is called network topology. AUMA offers different network topologies. Line topology Figure 7: Structure for line topology Max. FO cable range in km (observe technical data!) FO T-coupler within electrical connection of ACExC 01.2...
  • Page 9: Star Topology

    Network topologies As soon as the actuator is switched off (motor voltage), the FO connection board of Case B this actuator is no longer available. As a consequence, communication with the (option) subsequent actuators is lost. To prevent this, the complete ACExC 01.2 can be externally supplied with 24 V DC.
  • Page 10: Ring Topology (Two-Fibre Ring)

    Network topologies Ring topology (two-fibre ring) Figure 9: Structure for ring topology Max. FO cable range in km (observe technical data!) FO ring coupler within electrical connection of ACExC 01.2 FO ring coupler within DCS (imperatively required) FO ring coupler for any Profibus DP field device Any Profibus DP field device Information Maximum number of FO device (actuators) connected in series is 36.
  • Page 11 Network topologies Number of FO couplers within the ring Module run time of the signals within the FO coupler = 4.5 ms FO coupler Length of the FO cables within the ring Run time per metre FO = 5 ns The values indicated in the table apply to Profibus DP .
  • Page 12: Corrective Action

    Corrective action Corrective action LED indications Figure 10: LEDs on FO coupler [BA] Bus active (yellow) Operation (green) Fault channel 1/2 (multicolour) – ring coupler only Table 4: Summary of functions Function lour yellow LED flackert: Data from RS485 channel are transmitted via the optical interface. green LED is illuminated: Power supply (24 V DC) for FO coupler is available...
  • Page 13: Line And Star Topology

    Corrective action Furthermore, different fieldbus interface states can be requested via the A CExC 01.2 display (Menu Diagnostic M0022). For further information, please refer to “Manual (Device integration fieldbus) AC 01.2/ACExC 01.2”. 4.2.1 Line and star topology Table 5: Troubleshooting table Causes and remedies Can actuator be controlled →...
  • Page 14 Corrective action Causes and remedies Fault LED [F] illuminated? Ja: LED illuminated in red, → Continue with 5 yellow or orange? No (LED is not illuminated) → Continue with 6 Check connection to adja- Possible causes and remedies: cent FO coupler (fieldbus Receiver at FO coupler defective device): Sender at adjacent FO coupler defective...
  • Page 15: Technical Data

    The following technical data includes standard and optional features. For detailed information on the customer-specific version, refer to the order-relevant data sheet. This data sheet can be downloaded from the Internet at http://www.auma.com in German and English (indication of commission number required).
  • Page 16: Appendix

    Typical values for FST = 0.4 – 0.6 dB, for FSMA = 0.6 – 1.6 dB. Additional number of FO couplings within the FO cable between two actuators (excluding FO couplings at electrical connection of AUMA actuators; damping of these actuators is already included in the optical budget).
  • Page 17: Measuring Methods

    Appendix Measuring methods Figure 12: Damping measurement Reference addresses Required FO module for the master: BARTEC Top Holding GmbH Max-Eyth-Straße 16 D-97980 Bad Mergentheim Germany Tel.: +49 7931 597-0 Fax: +49 7931 597-119 www.bartec.de FO cables and wires: Network reliability despite multiple points of failure eks Engel GmbH &...