Actuator controls
AC 01.2/ACExC 01.2 Foundation Fieldbus
Change the device ad-
dress:
Change the PD tag:
Figure 6:
Tag and device address setting
A Foundation Fieldbus Device can take on three states. If the state does not
correspond to the SM_OPERATIONAL state, no function block will be executed
Figure 7:
AUMATIC default setting:
PD tag: AUMA AC 01.2
Address: 247 (0xF7
).
hex
If two AUMATIC actuator controls are connected to the same address within the
same Foundation Fieldbus network, one of the controls keeps the address assigned,
whereas the other device uses a default address (from 248 [or 0xF8
0xFB
]).
hex
1.
Delete the address (CLEAR_ADDRESS).
2.
Assign new, unused address (SET_ADDRESS).
1.
Delete address and PD tag.
2.
Then, assign again PD tag and address.
Devices for which the address has been deleted will wait within the default address
range for a new setting (randomly chosen from a range of 248 (or 0xF8
(or 0xFB
). At the same time, the device ID must be known to clearly identify the
hex
device. The worldwide unique device ID for the AUMATIC is
0A01FF0001WorksNoxSerialNo.
Commissioning
] to 251 [or
hex
) to 251
hex