AUMA AUMATIC AC 01.2 Manual page 36

Actuator controls foundation fieldbus
Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Commissioning
CHANNEL parameter
Ch DITB actuator signals [8 bit]
Ch DITB device status [8 bit]
Ch DITB operation status [8
bit]
Ch DITB intermediate positions
[8 bit]
Ch DITB discrete inputs [8 bit]
36
Value
Used Trans-
ducer Block
23
DITB
24
DITB
25
DITB
26
DITB
27
DITB
AC 01.2/ACExC 01.2 Foundation Fieldbus
Explanation
Actuator signals
Bit 0: Thermal fault
Bit 1: Phase failure
Bit 2: Selector sw. REMOTE
Bit 3: Selector sw. LOCAL
Bit 4: Limit switch OPEN
Bit 5: Limit switch CLOSED
Bit 6: Torque switch OPEN
Bit 7: Torque switch CLOSE
Device status
Bit 0: Not ready REMOTE
Bit 1: Warnings
Bit 2: Fault
Bit 3: Maintenance required
Bit 4: Out of specification
Bit 5: Function check
Bit 6: Failure
Bit 7: Device ok
Operation status
Bit 0: Op. pause active
Bit 1: In intermed. position
Bit 2: Start stepping mode
Bit 3: -
Bit 4: Actuator running
Bit 5: Handwheel oper.
Bit 6: Running REMOTE
Bit 7: Running LOCAL
Intermediate positions
Bit 0: Intermediate pos. 1
Bit 1: Intermediate pos. 2
Bit 2: Intermediate pos. 3
Bit 3: Intermediate pos. 4
Bit 4: Intermediate pos. 5
Bit 5: Intermediate pos. 6
Bit 6: Intermediate pos. 7
Bit 7: Intermediate pos. 8
Discrete inputs
Bit 0: Input DIN 1
Bit 1: Input DIN 2
Bit 2: Input DIN 3
Bit 3: Input DIN 4
Bit 4: Input DIN 5
Bit 5: Input DIN 6
Bits 6, 7: -