REFNET Pipe System

4. REFNET Pipe System
4.1

Layout Example

4.1.1 Heat Pump System
Use of the particular branch fitting appropriate to each individual unit type not only permits the pipes to be laid
with ease but also increases the reliability of the system as a whole.
Type of
fitting
Units can be added by connecting them directly to the REFNET header or REFNET joint. Further branches cannot be
included in the system below the REFNET header branch.
Notes:
1. When the capacity ratio of the indoor system to the outdoor unit is more than 100% and when all the indoor units are
in operation at the same time, the rated capacity of each unit will be somewhat reduced.
2. Special purpose REFNET pipe components must be used for all the pipe work. For further details concerning
choosing components, see REFNET and Piping Selection Rules.
3. The Daikin REFNET kits are supplied with insulation intended to fit over the main body of the REFNET joint after
installation of the REFNET kit is complete.
4. IMPORTANT: In applications where the REFNET kits are installed in an environment requiring fire-rated materials to
be used, it is necessary for the installer to obtain from a third party supplier and to utilize, for insulation, fire-rated
materials that meet all applicable building codes and other requirements. The Factory-provided insulation that is
supplied with the REFNET kit should be discarded in a manner meeting all applicable laws.
54
Sample systems
EDUS341411-N
Installation of Outdoor Units