Daikin VRV IV RXYQ TYDN Series Engineering Data page 32

Table of Contents

Advertisement

EDUS341411-N
RXYQ72T
[R410A] Label
handling the stop valve.
The refrigerant charge port is connected to unit pipe. When
shipped, the unit contains the refrigerant, so use caution when at-
taching the charge hose.
<Air tight test>
Pressurize the liquid pipe, gas pipe, and equalizer pipe from the ser-
hours, the system passes the test.
If there is a pressure drop, check for leaks, make repairs and perform
the air tight test again.
<Vacuum drying>
vice ports by using a vacuum pump for more than 2 hours and bring
the system to 500 microns or less. After keeping the system under that
condition for more than 1 hour, check if the vacuum gauge rises or not.
If it rises, the system may either contain moisture inside or have leaks.
NOTE
During the rainy season, moisture might enter the piping. If
working during a rainy season and the work takes long enough
for condensation to form inside the pipes, take the following
precautions:
After evacuating the system for 2 hours, pressurize the system to
the system again using the vacuum pump for 1 hour to 500 microns or
less (vacuum drying).
repeat the operation of vacuum break and vacuum drying.
vacuum gauge does not rise.
11. Pipe insulation
Insulation of pipes should be done after performing 10. Air tight test
Always insulate the liquid piping, the gas piping, the equalizer pipes
(between the outdoor units for the outdoor multi system) and pipe
connections.
Failing to insulate the pipes may cause leaking or burns.
Be sure to use insulation designed for HVAC equipment.
23
Installation of Outdoor Units
RXYQ96-168T
[R410A] Label
-
Reinforce the insulation on the refrigerant piping according to the
installation environment. Condensation might form on the surface of
the insulation. Refer to the below.
- Ambient temperature : 86°F (30°C), humidity : 75% to 80% RH :
minimum thickness : 9/16 in. (15 mm).
-
80% RH, then the minimum thickness is 3/4 in. (20 mm).
If there is a possibility that condensation on the stop valve might
drip down into the indoor unit through gaps in the insulation and
piping because the outdoor unit is located higher than the indoor
unit, this must be prevented by caulking the connections. (Refer to
3
4
2
1
1
5
12. Checking of device and installation conditions
Be sure to check the followings.
For those doing electrical work
1 Make sure there is no faulty transmission wiring or loosening of a
nut.
2 Make sure there is no faulty power wiring or loosening of a nut.
3 Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular
value in accordance with relevant local and national regulations.
For those doing pipe work
1 Make sure piping size is correct.
2 Make sure insulation work is done.
See 11. Pipe insulation.
3 Make sure there is no faulty refrigerant piping.
13.
required to give some input to the logic board of the unit. This chapter
will describe how manual input is possible by operating the push but-
tons/DIP switches on the logic board and reading the feedback from
the 7 segment displays.
Installation Manual
1 Insulation material
2 Caulking, etc.
3 Liquid pipe stop valve
4 Gas pipe stop valve
5 Connection pipe
-
3P362438-1B English
3P362438-1B
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents