REFNET Joint and Header
5.3

Outdoor Unit Multi Connection Piping Kit

BHFP22P100U
Gas side
1-9/16
I. D. φ 3/4
to Outdoor
I. D. φ 7/8
Unit B
I. D. φ 1
I. D. φ 1-1/8
Accessory
GAS-SIDE JOINT : 1
LIQUID-SIDE JOINT : 1
GAS-SIDE REDUCER (1) : 1
GAS-SIDE REDUCER (2) : 1
GAS-SIDE REDUCER (3) : 1
GAS-SIDE REDUCER (7) : 1
GAS-SIDE REDUCER (9) : 1
LIQUID-SIDE REDUCER (1) : 1
LIQUID-SIDE REDUCER (3) : 1
LIQUID-SIDE REDUCER (5) : 1
INSULATION MATERIAL FOR GAS-SIDE JOINT : 1
INSULATION MATERIAL FOR LIQUID-SIDE JOINT : 1
INSULATION MATERIAL FOR GAS-SIDE PIPE : 1
INSULATION MATERIAL FOR LIQUID-SIDE PIPE : 1
INSTALLATION MANUAL
Liquid side
to Outdoor
Unit B
I. D. φ 3/8
I. D. φ 1/2
Accessory
GAS-SIDE JOINT : 1
LIQUID-SIDE JOINT : 1
GAS-SIDE REDUCER (1) : 1
GAS-SIDE REDUCER (2) : 1
GAS-SIDE REDUCER (3) : 1
GAS-SIDE REDUCER (7) : 1
GAS-SIDE REDUCER (9) : 1
LIQUID-SIDE REDUCER (1) : 1
LIQUID-SIDE REDUCER (3) : 1
LIQUID-SIDE REDUCER (5) : 1
INSULATION MATERIAL FOR GAS-SIDE JOINT : 1
INSULATION MATERIAL FOR LIQUID-SIDE JOINT : 1
INSULATION MATERIAL FOR GAS-SIDE PIPE : 1
INSULATION MATERIAL FOR LIQUID-SIDE PIPE : 1
INSTALLATION MANUAL
70
GAS-SIDE JOINT + GAS-SIDE REDUCER (1)
to Outdoor Unit A
3-1/16
24-15/16
2-5/8
24-7/16
23-1/16
I. D. φ 3/4
I. D. φ 7/8
I. D. φ 1
INSULATION MATERIAL
I. D. φ 1-1/8
FOR GAS-SIDE JOINT
Gas-Side Reducer
Local Brazing
Gas-Side Joint
1/16
1-3/8
27-15/16
GAS-SIDE REDUCER (2) ( φ 1-1/4)
4-3/4
4-3/16
I. D. φ 1-1/2
Outdoor Unit B
Elbow
(Field Supplied Parts)
Layout Drawing (Upper-Side)
LIQUID-SIDE JOINT + LIQUID-SIDE REDUCER (1)
to Outdoor
I. D. φ 3/8
Unit A
I. D. φ 1/2
Liquid-Side
Reducer (1)
Local Brazing
I. D. φ 5/8
Caution
Liquid-Side
Label
Joint
5/8
8-13/16
10
11-3/16
9/16
11-5/8
12-7/16
Outdoor Unit A
Outdoor Unit B
Layout Drawing (Upper-Side)
to Indoor
Unit
I. D. φ 1-1/8
I. D. φ 1-1/4
Caution Label
A
Outdoor Unit A
±15˚
or Less
to Indoor Unit
Gas-Side Joint
ARROW VIEW A
INSULATION MATERIAL
FOR LIQUID-SIDE JOINT
I. D. φ 7/8
I. D. φ 3/4
to Indoor Unit
NOTE) 1. "- - - -" in the figure show field supply piping.
2. About size of connection pipe refer the "engineering data of VRV III".
3. In case of install this kit observe follow conditions.
· Do not tilt the joint more than ±15˚.
Install the joint horizontally so that the caution label attached to joint comes to the top.
· Do not install the joint vertically why it may cause the malfunction of outdoor unit.
· Make sure the piping up to the joint is straight for more than 19-11/16in. Do not bend
the field piping within this range.
If a straight field piping more than 4-3/4in is connected, more than 19-11/16in of
straight section can be ensured.
View 1
A
to Indoor Unit
±15˚
Liquid-Side Joint
or Less
ARROW VIEW A
GAS-SIDE REDUCER (3) ( φ 1)
I. D. φ 1-1/8
I. D. φ 1
I. D. φ 7/8
I. D. φ 3/4
3/8
1-9/16
3
4-7/16
6-1/2
11-3/4
NOTE)
1. "- - - -" in the figure show field supply piping.
2. About size of connection pipe refer the "engineering data of VRV III".
3. In case of install this kit observe follow conditions.
· Do not tilt the joint more than ±15˚.
Install the joint horizontally so that the caution label attached to joint
comes to the top.
· Do not install the joint vertically why it may cause the malfunction of
outdoor unit.
· Make sure the piping up to the joint is straight for more than 19-11/16in.
Do not bend the field piping within this range. If a straight field piping
more than 4-3/4in is connected, more than 19-11/16in of straight section
can be ensured.
×
View 1
View 2
B
Caution Label
Caution Label
×
Ground
Ground
ARROW VIEW B
×
View 2
B
Caution Label
Caution Label
×
Ground
Ground
ARROW VIEW B
Installation of Outdoor Units
EDUS341411-N
Unit: in.
1-15/16
View 3
Local Piping
(Length 4-3/4in or More)
3D060136
Unit: in.
View 3
Local Piping
(Length 4-3/4in or More)
3D060135