Daikin VRV IV RXYQ TYDN Series Engineering Data page 21

Table of Contents

Advertisement

Installation Manual
7.5.2. System only containing VRV indoor units
System setup
Single outdoor
Multi outdoor
Indoor unit
Refnet joint
Refnet header
Outdoor multi con-
nection piping kit
Difference in height between outdoor and indoor units: H1.
Difference in height between indoor and indoor units: H2.
Difference in height between outdoor and outdoor units: H3.
Difference in height between outdoor and BP unit: H4.
Difference in height between BP unit and BP unit: H5.
Difference in height between BP unit and Mini-split indoor unit: H6.
Example 3: with standard multi layout
r
Maximum allowable length
Between outdoor and indoor units (standard multi/free multi combinations)
Actual piping
length
Equivalent length
Total piping length 3280 ft.
Between outdoor branch and outdoor unit
Actual piping
length
Equivalent length
3P362438-1B English
22
Branch with refnet joint
a
b
c
d
e
f
A
B
C
D
E
F
h
i
j
k
l
1
2
3
4
5
Example 1.1
H3
r
s
t
u
a
b
c
d
e
A
B
C
D
E
h
i
j
k
l
1
2
3
4
5
Example 2.1
s
t
540 ft.
Example 1.1
(165 m)
unit 8: a+b+c+d+e+f+g+p 540 ft. (165 m)
Example 2.1
unit 8: a+b+c+d+e+f+g+p 540 ft. (165 m)
(2)
623 ft.
(190 m)
Example 1.1
(1000 m)
a+b+c+d+e+f+g+h+i+j+k+l+m+n+p 3280 ft. (1000 m)
Example 2.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+p 3280 ft. (1000 m)
33 ft. (10 m) Example 3
r 33 ft. (10 m)
s 33 ft. (10 m)
t 33 ft. (10 m)
43 ft. (13 m)
Branch with refnet joint and refnet header
a
A
g
b
H1
H1
G
p
m
n
c
d
e
6
7
1
2
3
8
H2
Example 1.2
H3
t
r
s
u
a
f
g
H1
A
b
F
G
p
m
n
6
7
c
d
e
f
8
1
2
3
4
Example 2.2
Example 1.2
unit 6: a+b+h 540 ft. (165 m)
unit 8: a+i+k 540 ft. (165 m)
Example 1.2
a+b+c+d+e+f+g+h+i+j+k
3280 ft. (1000 m)
Maximum allowable height difference
H1
164 ft. (50 m ) (130 ft. (40 m)
H2
98 ft. (30 m)
H3
16 ft. (5 m)
(a)
kit:
Liquid piping size up (see table Size up for equivalent length for outdoor-
130-197 ft. (40-60 m): minimum connection ratio connected: 80%.
197-213 ft. (60-65 m): minimum connection ratio connected: 90%.
213-262 ft. (65-80 m): minimum connection ratio connected: 100%.
262-295 ft. (80-90 m): minimum connection ratio connected: 110%.
Liquid piping size up (see table Size up for equivalent length for outdoor-indoor
Branch with refnet header
i
a
B
k
j
7
8
H2
b
c
d
e
f
f
g
h
1
2
3
4
5
4
5
6
Example 1.3
t
r
s
u
H1
a
B
j
k
7
8
H2
g
h
b
c
d
e
5
6
1
2
3
4
5
Example 2.3
Example 1.3
unit 8: a+i 540 ft. (165 m)
Example 1.3
a+b+c+d+e+f+g+h+I
3280 ft. (1000 m)
(a)
(if outdoor is located below indoor units))
Installation of Outdoor Units
EDUS341411-N
H1
g
h
i
6
7
8
H2
H3
H1
f
g
h
i
6
7
8
12