If there are any steps you do not
complete or if you respond with 'No',
please explain in the comments field!
Controller settings
1
Which potable water temperature
was set?
2
Was the circulation activated (see
the circulation section in the con-
troller operating instructions)?
2.1 Which mode was activated?
3
Is the controller LED lit up green?
4
Have additional changes been
made to the controller settings?
If there are any steps you do not
complete or if you respond with 'No',
please explain in the comments field!
Final inspection
1
Was the installation checked for
leaks (DIN EN 806)?
2
Was commissioning carried out
in accordance with the operating
instructions?
Instruction/Handover
The installer is responsible for briefing the user on the functions and intended use of the fresh water
station.
The installer is responsible for pointing out the correct operation of potable water installations to the
user.
The installer has provided the user with the necessary documents.
Information on correct operation of potable water systems:
- Stagnation must be avoided; a regular exchange of the potable water must be ensured
- TPWH must be maintained at >= 60 °C at the hot water outlet
- The circulation system must be designed in such a way that the potable water temperature does not fall more
than 5 K below the station outlet temperature of >= 60 °C
- TPWC must be maintained at < 25 °C at the cold water outlet
Installer / Installation company
_____________________________________________________________
Date / Signature / Stamp
User
Handover report received
_____________________________________________________________
Date / Signature
Tick as appropriate or
enter a value/number
Yes
No
°C
¨
¨
¨
¨
¨
¨
Tick as appropriate or
enter a value/number
Yes
No
¨
¨
¨
¨
Comments/settings
Comments/settings
¨
¨
¨