Troubleshooting
MALFUNCTION
The LED on the controller
flashes red.
An error code appears on the
display.
The error message is au-
(
tomatically reset once the
error has been resolved.)
Water escaping or leakage outside
the heat exchanger.
Pressure increase in the storage
cylinder circuit (potable water en-
ters the storage cylinder circuit).
The safety valve in the storage
cylinder circuit opens.
The discharge capacity is too low
at the draw-off points.
9.2

Nominal resistances of the temperature sensors

°C
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
38
CAUSE
S1, Sensor storage cylinder supply
E1
defective
S2, Sensor hot water temperature
E2
defective
S3, Sensor cold water/circulation
E3
defective
E4
(LIN) pump error
Leakage from the heat exchanger due
to corrosion. This may be due to the
heat exchanger not being suitable for
the potable water quality.
The heat exchanger is severely calci-
fied.
The cold water pressure is too low
(wrongly set pressure reducer).
Ω
Pt1000
961
980
1000
1019
1039
1058
1078
1097
1117
1136
1155
1175
1194
1213
1232
1252
1271
1290
1309
1328
1347
1366
1385
1404
1423
"Regumaq X-25"
REMEDY
Replace the sensor.
Replace the sensor.
Replace the sensor.
Replace the pump.
Replace the heat exchanger. The
brazing material used for the new
heat exchanger has to match the po-
table water quality (see information
sheet "Important advice regarding
corrosion protection" in appendix).
Decalcify the potable water side of
the heat exchanger.
Check the setting of the pressure
reducer. Increase the pressure if
necessary.
°C
115
138112581-V01.10.2019
Ω
Pt1000
1442