Emc Limit Values In South Korea - Siemens SINAMICS G120P Hardware Installation Manual

Power module pm230, ip20 / push through
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

EMC / Immunity
The Power Modules have been tested in accordance with the immunity requirements of
category C3 – Second Environment – and fulfill the requirements according 61800-38.
Note
The immunity requirements apply equally to both filtered and unfiltered Power Modules.
Harmonic currents
Typical harmonic current (% of rated input current) at U
Note
Installation of Power Modules in an environment of category C2
Power Modules, which are installed in an environment of category C2, require a connection
approval for the low-voltage supply system. Contact your local supply system operator in this
case.
A.2.3

EMC limit values in South Korea

(A
The EMC limit values to be complied with for South Korea correspond to the limit values of
the EMC product standard for variable-speed electric drives EN 61800-3, Category C2 or
limit value class A, Group 1 according to EN55011. By applying suitable supplementary
measures, the limit values according to Category C2 or according to limit value class A,
Group 1 are maintained. Further, additional measures may be required, for instance, using
an additional radio interference suppression filter (EMC filter). The measures for EMC-
compliant design of the system are described in detail in this manual respectively in the
Installation Guideline EMC.
Please note that the final statement on compliance with the standard is given by the
respective label attached to the individual unit.
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA
5.
7.
21
15
)
11.
13.
10
9
.
A.2 Electromagnetic compatibility
1 %
K
17.
19.
7
6
Appendix
23.
25.
6
5
,
59

Advertisement

Table of Contents
loading