2 Product information

2.1

Safety advice

2.2

Intended use

2.2.1

Areas of use

2.3

Product description

2.3.1

Overview and description of component

Scope of delivery
Flush valve universal
DANGER!
Danger due to electrical current
An electric shock can lead to burns and serious injury and
even death.
– Work on the electrics may only be carried out by trained
electricians.
– Switch off the mains voltage before carrying out work on
electrical parts.
The flush valve is intended for use in drinking water installations with
manifold or uptake conduits of dimension 12-80.
While an external flush command is applied, the control of the flush
valve automatically performs a water exchange, helping the user to
keep their water quality at drinking water level.
The control does not perform a water exchange independ-
ently or automatically. Water exchange must be triggered
by enabling the binary input referred to a potential, or the
analog voltage input (6-48 V AC/DC). This opens the inte-
grated magnet valve for as long as the signal is applied.
The flush valve must either be connected to a higher-level control, such
as building control system (= BCS) which centrally monitors the fault
and alarm message outputs and evaluates the signals, or a once-per-
week visual inspection of the alarms indicated at the control must be
ensured.
Flush valve, mounted to the base support, with interior wiring
n
fixing material
n
n
Seals for inlet and drain
Product information
7 from 62