Components And Physical Data - Carrier 19XRV Series Start-Up And Service Instructions

With pic iii/pic 6 controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

Components and Physical Data

The 19XRV chillers use the Allen-Bradley PF755 Frame 6 drive
for
the
230-amp rated
19XVR0230...). See Fig. 6.
The Allen-Bradley PF755 Frame 7 drive is used for the 335-amp
and 445-amp rated application (Carrier Part No. 19XVR0335...
and 19XVR0445...). See Fig. 7.
21P - 19XRV Std Tier
Voltage Code
1 – 480 vac, 60 Hz
2 – 380 vac, 50 Hz
3 – 380 vac, 60 Hz
4 – 400 vac, 50 Hz
5 – 400 vac, 60 Hz
6 – 415 vac, 50 Hz
7 – 415 vac, 60 Hz
Full Load Amp Rating
(Maximum Continuous Amps)*
0248 – 248
0361 – 361
0477 – 477
* For Carrier applications, maximum continuous amp ratings
are 230, 335, and 445.
Fig. 4 — Rockwell Automation Drive Assembly Catalog Number Nomenclature: 19XRV Units
21PB - 23XRV Std Tier
Voltage Code
1 – 480 vac, 60 Hz
2 – 380 vac, 50 Hz
3 – 380 vac, 60 Hz
4 – 400 vac, 50 Hz
6 – 415 vac, 50 Hz
7 – 415 vac, 60 Hz
8 – 600 vac, 60 Hz
Full Load Amp Rating
(Maximum Continuous Amps)*
0248 – 248
0289 – 289
0361 – 361
0477 – 477
* For Carrier applications, maximum continuous amp ratings are 230, 269, 335, and 445.
† For 600 v applications, CB1 = 65 KAIC and CB2 = 42 KAIC rating (575 v).
Fig. 5 — Rockwell Automation Drive Assembly Catalog Number Nomenclature: 23XRV Units
application (Carrier Part
21P - 1
0248
21PB - 1
0248
See Fig. 8 for the dimensions of Frames 6 and 7 for 19XRV
chillers.
The 23XRV chiller uses the Frame 7 drive for 335-amp and 455-
No.
amp rated applications (Carrier Part No. 23XVR0335... and
23XVR0445...). Frame 6 is not used.
See Fig. 9 for the dimensions of Frame 7 for 23XRV chillers.
- 3
5
0
Meter Option
0 – No Meters
2 – Digital Meter
Input Device
3 – 65 KAIC Capacity Breaker
4 – 100 KAIC Capacity Breaker
Enclosure
4 – Unit Mount Type 1/IP23 Liquid Cooled
5 – Unit Mount Type 1/IP23 Liquid Cooled/Air Filter
a19-2380
-
4
3
0
0
0
CE (Conformité Européenne)
0 – No
1 – Yes
Control Power
0 – Standard
1 – High
Meter Option
0 – No Meters
2 – Digital Meter
Input Device
3 – 65 KAIC Capacity Breaker
4 – 100 KAIC Capacity Breaker
Enclosure
1 – Unit Mount Type 1/IP23 Air Cooled/Filter
4 – Unit Mount Type 1/IP23 Liquid Cooled
4
a19-2381